Type 11
Type 11 is a two-wire run mode configuration. It requires only two wires
and one relay to control the generator. Relay 1 closes momentarily once
to start the generator, and closes momentarily again to stop the
generator.
Figure 2-19 Type 11 Connection Diagram
Table 2-15 Type 11 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
MomentaryRun
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
10 s
Crank retry time
15 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
0 s
Start tries
3
XW AGS Harness Wires Generator Wires
16
14
13
12
Relay 1
5A fuse
GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
RUN
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN