Product Manual

Installation
2–14 975-0307-01-01
Type 5
Type 5 is a three-wire StartStop configuration that uses relay 3 to provide
a 15-second preheat signal.
Figure 2-11 Type 5 Connection Diagram
Table 2-9 Type 5 Relay and Timing Preset Configurations
Relay Function
Preset Configuration
Setting
Relay 1 mode
StartStop
Relay 3 mode
Preheat
Gen Run signal hold
time
2 s
Preheat time
15 s
Preheat to crank delay
2 s
Crank time
15 s
Crank retry time
15 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
0 s
Start tries
3
XW AGS Harness Wires Generator Wires
18
17
16
14
13
12
20
19
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY +
Relay 1
Relay 3
Relay 2
5A fuse
5A fuse
5A fuse
GENERATOR RUN SIGNAL
STOP/PREHEAT
START
GENERATOR BATTERY NEGATIVE (–)
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
START
STOP/PREHEAT
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY +