Product Manual
Installation
2–12 975-0307-01-01
Type 3
Type 3 is a three-wire GlowStop with shutdown bypass configuration. The
configuration shown in Figure 2-9 uses a shutdown bypass output to
temporarily disable the generator’s low oil pressure shutdown
functionality during cranking. Generators with this functionality often
have a manual means of disabling it during cranking.
Figure 2-9 Type 3 Connection Diagram
Table 2-7 Type 3 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
GlowStop/Shutdown bypass
Relay 3 mode
Preheat/Shutdown bypass
Gen Run signal hold
time
0.5 s
Preheat time
20 s
Preheat to crank delay
0 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
10 s
Start tries
3
XW AGS Harness Wires Generator Wires
14
13
12
18
17
16
Relay 1
Relay 2
5A fuse
5A fuse
GENERATOR RUN SIGNAL
START
PREHEAT
STOP
BYPASS SHUTDOWN
GENERATOR BATTERY NEGATIVE (–)
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
PREHEAT
START
STOP
BYPASS SHUTDOWN