Product Manual
Installing the Xantrex XW Automatic Generator Start
975-0307-01-01 2–11
Type 2
Type 2 is a three-wire GlowStop configuration recommended for “three-
wire” generators that don’t require a dedicated preheat signal. In this
configuration, the start signal is applied for longer because the generator
does its own preheat and cranking while the start signal is applied.
Figure 2-8 Type 2 Connection Diagram
Table 2-6 Type 2 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
GlowStop
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
30 s
Crank retry time
40 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
0 s
Start tries
3
18
17
16
14
13
12
Relay 1
Relay 2
5A fuse
5A fuse
XW AGS Harness Wires Generator Wires
GENERATOR RUN SIGNAL
START
RUN
GENERATOR BATTERY NEGATIVE (–)
For additional information, see
“Circuit Limitations” on page 2–5.
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN
START