Dimensions in in.
A: 1.18in. min.
B: 1.57in. min.
General Tolerances of the Panel and Printed Circuit Board
The cumulative tolerance must not exceed 0.3mm / 0.012in: T1 + T2 = 0.3mm max.
Installation Precautions
● Minimum thickness of circuit board: 1.6mm / 0.06in.
● Cut-out diameter: 22.4mm ± 0.1 / 0.88in. ± 0.004
●
Orientation of body/fixing collar ZB4BZ009: ± 2
°
30’ (excluding cut-outs marked a and b).
● Tightening torque of screws ZBZ006: 0.6N.m (5.3lbf.in) max.
● Allow for one ZB4BZ079 fixing collar/pillar and its fixing screws:
○ every 90mm / 3.54in. horizontally (X), and 120mm / 4.72in. vertically (Y).
○ with each selector switch head (ZB4BD•, ZB4BJ•, ZB4BG•).
The fixing centers marked a and b are diagonally opposed and must align with those marked 4 and 5.
(1) Panel
(2) Printed circuit board