Characteristics
Electrical characteristics
Characteristics of the application program
Characteristics of the CANopen communication port
Power Voltage V 24 c (min. 19, max. 30)
Current consumption Maximum A 2
No-load mA 80
Using logic output mA 200 maximum (1)
Analog inputs AI51, AI52 2 current analog inputs 0…20 mA, impedance 250 Ω
Resolution: 10 bits
Accuracy: ± 1% for a temperature variation of 60°C
Linearity: ± 0.2% of the maximum value
Common point for all the card I/O (2)
Analog outputs AO51, AO52 2 current analog outputs 0…20 mA, impedance 500 Ω
Resolution: 10 bits
Accuracy: ± 1% for a temperature variation of 60°C
Linearity: ± 0.2% of the maximum value
Common point for all the card I/O (2)
Logic inputs LI51…LI60 10 logic inputs, 2 of which can be used for 2 counters or 4 of which can
be used for 2 incremental encoders
Impedance 4.4 kΩ
Maximum voltage: 30 V c
Switching thresholds:
State 0 if y 5 V or logic input not wired
State 1 if u 11 V
Common point for all the card I/O (2)
Logic outputs LO51…LO56 Six 24 V c logic outputs, positive logic open collector type (source),
compatible with level 1 PLC, standard IEC 65A-68
Maximum switching voltage: 30 V
Maximum current: 200 mA
Common point for all the card I/O (2)
I/O connection Type of contact Screw, at intervals of 3.81 mm
2
Maximum wire mm
2
1.5 (AWG 16)
Tightening torque
Nm
0.25
Lithium battery Life 8 years approx.
Compiled program
(saved in “flash” memory)
Maximum size Kb 320
Data Maximum size Kword 64
Saved size (NVRAM) Kword 4
Size accessible by
Modbus
Kword 2
Structure Connector One 9-way male SUB-D connector
Network management Master
Transmission speed Configurable via the program:
50 kbps, 125 kbps, 250 kbps, 500 kbps or 1 Mbps
Address (Node ID) 32 slaves maximum
Services CANopen application
layer
DS 301 V4.02
Channel config. DSP 405
PDO 9 receive and transmit PDOs in total for each slave
SDO 2 client SDOs per slave (1 read and 1 write). Block transfer
Error check Node Guarding, producer and consumer Heartbeat
Other services Emergency, Boot-up, Sync
Configuration The CANopen network configurator is integrated in the PS1131 software
workshop.
Diagnostics Using LEDs 2 LEDs: “RUN” and “ ERROR”, conforming to CIA DR303 version 1.0
(1) If the power consumption table does not exceed 200 mA, this card can be powered by the drive. Otherwise, an external 24 V
c
power supply must be used.
(2) This common point is also the drive 0 V (COM).