Installation manual
31
Option terminals
Terminal Function Electrical characteristics
+24 Logic input power supply Switch SW4 in Source or Sink Int position
•+24 V c output (min. 21 V, max. 27 V), protected against short-circuits and overloads
• Max. current available for customers 200 mA (This current corresponds to the total
consumption on the control card +24 and the option cards +24)
Switch SW4 in Sink Ext position
• Input for external +24 V c power supply for the logic inputs
LI11
LI12
LI13
LI14
Programmable logic inputs • +24 V c (max. 30 V)
• Impedance 3.5 kΩ
• Reaction time: 5 ms ± 1 ms
0V Logic input common 0 V
TH2 +
TH2 -
PTC probe input • Trip threshold 3 kΩ, reset threshold 1.8 kΩ
• Short-circuit detection threshold < 50Ω
RP Frequency input • Frequency range: 0…30 kHz
• Cyclic ratio: 50% ± 10%
• Maximum sampling time: 5 ms ± 1 ms
• Maximum input voltage 30 V, 15 mA
• Add a resistor if the input voltage is greater than 5 V (510 Ω for 12 V,
910 Ω for 15 V, 1.3 kΩ for 24 V)
• State 0 if < 1.2 V, state 1 if > 3.5 V
LO3
LO4
Open collector programmable logic
outputs
•+24 V c (max. 30 V)
• Max. current 20 mA for internal power supply and 200 mA for external power supply
• Reaction time 5 ms ± 1 ms
CLO Logic output common
0V 0 V 0 V
Switch SW4 State 0 State 1
Source (factory setting) < 5 V c > 11 V c
Sink Int or Sink Ext > 16 V c < 10 V c