Installation manual
29
Option terminals
Logic I/O option card terminals (VW3 A3 201)
Maximum wire size:
1.5 mm² - AWG 16
Max. tightening torque:
0.25 Nm - 2.21 lb.in
Characteristics and functions of the terminals
Terminal Function Electrical characteristics
R3A
R3B
R3C
Common point C/O contact R3C
of
programmable relay R3
• Minimum switching capacity: 3 mA for 24 V c
• Maximum switching capacity on resistive load:
5 A for 250 V a or 30 V c
• Maximum switching capacity on inductive load (cos ϕ = 0.4 L/R = 7 ms):
2 A for 250 V a or 30 V c
• Reaction time: 7 ms ± 0.5 ms
• Service life: 100,000 operations
-10 -10 V c power supply for reference
potentiometer 1 to 10 k
Ω
•- 10 V c (-10.5 V ± 0.5V)
• 10 mA max.
+24 Logic input power supply Switch SW3 in Source or Sink Int position
• +24 V c power supply (min. 21 V, max. 27 V), protected against short-circuits
and
overloads
• Max. current available for customers 200 mA (This current corresponds to the total
consumption on the control card +24 and the option cards +24)
Switch SW3 in Sink Ext position
• Input for external +24 V c power supply for the logic inputs
LI7
LI8
LI9
LI10
Programmable logic inputs • +24 V c power supply (max. 30 V)
• Impedance 3.5 kΩ
• Reaction time 2 ms ± 0.5 ms
0 V 0 V 0 V
TH1+ PTC probe input • Trip threshold 3 kΩ, reset threshold 1.8 kΩ
• Short-circuit detection threshold < 50Ω
TH1-
LO1
LO2
Open collector programmable
logic
outputs
• +24 V c (max. 30 V)
• Max. current 200 mA for internal power supply and 200 mA for external power supply
• Reaction time: 2 ms ± 0.5 ms
CLO Logic output common
0V 0 V 0 V
R3A
TH1+
SW3
R3C
R3B
0V
-10
+24
LI7
LI8
LI9
LI10
TH1-
L01
L02
CLO
0V
Ext
Source
Sink
Int
Logic input switch SW3
Factory setting: Source
Switch SW3 State 0 State 1
Source (factory setting) < 5 V c > 11 V c
Sink Int or Sink Ext > 16 V c < 10 V c