Installation manual

27
Control terminals
Access to the control terminals
To access the control terminals,
open the cover on the control front panel.
Removing the terminal card
To make it easier to wire the drive control section, the control
terminal card can be removed.
• Undo the screw until the spring is fully extended
• Remove the card by sliding it downwards
Arrangement of the control terminals
Maximum wire size:
2.5 mm² - AWG 14
Max. tightening torque:
0.6 Nm - 5.3 lb.in
Note: The ATV71 is supplied with a link between the PWR and +24 terminals.
CAUTION
IMPROPERLY SECURED TERMINAL CARD
When replacing the control terminal card, it is essential
to
fully tighten the captive screw.
Failure to follow this instruction can result in injury
and/or equipment damage.
1
2
R1B
R1A
R1C
R2A
R2C
AI1+
+10
AI1-
COM
AI2
COM
AO1
0V
P24
LI1
LI2
LI3
LI4
LI5
LI6
+24
PWR
RJ45
SW1
SW2
Ext
Source
Sink
Int
PTC LI
Logic input switch
LI6 input switch
RJ45 connector
Factory setting: Source
Factory setting: LI