Installation manual

13
Mounting and temperature conditions
Install the drive vertically at ± 10°.
Do not place it close to heating elements.
Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the bottom
to the top of the unit.
Free space in front of the drive: 10 mm (0.39 in.) minimum
When IP20 protection is adequate, it is recommended that the protective cover on the top of the drive is removed
as shown below.
Removing the protective cover
Two types of mounting are possible:
ATV71H 037M3 to D15M3X and ATV71H 075N4 to D18N4 ATV71H D18M3X to D45M3X, ATV71H D22N4 to D75N4
and
ATV71H U22Y to D90Y
Type A
mounting
Free space u 50 mm (u 1.97 in.) on each side, with protective cover fitted
Type B
mounting
Drives mounted side by side, with the protective cover removed (the degree of protection becomes IP20)
u 100 mm
u 3.94 in.
u 100 mm
u 3.94 in.
u 50 mm
u 1.97 in.
u 50 mm
u 1.97 in.