Installation manual
11
Drive ratings
Three-phase supply voltage: 500…690 V 50/60 Hz
Three-phase motor 500...690 V
(1)These power ratings and currents are given for an ambient temperature of 50°C (122°F) at the factory-set switching frequency, used in
continuous operation (factory-set switching frequency of 4 kHz for ATV71H U22Y to D30Y and 2.5 kHz for ATV71H D37Y to D90Y).
Above this factory setting, the drive will reduce the switching frequency automatically in the event of excessive temperature rise.
For
continuous operation above the factory setting, derating must be applied to the nominal drive current in accordance with the
curves
on page 15.
(2)Current on a line supply with the “Max. prospective line Isc” indicated and for a drive without any external options.
Note:
The maximum transient current for 60 s corresponds to 150% of the maximum nominal current In.
The maximum transient current for 2 s corresponds to 165% of the maximum nominal current In.
Motor Line supply (input) Drive (output) Altivar 71
Power indicated on plate (1) Max. line current (2) Max.
prospective
line Isc
Max. available
nominal current In (1)
Catalog number
500 V 575 V 690 V at 500 V at 600 V at 690 V 500 V 575 V 690 V
kW HP kW A A A kA A A A
1.5 2 2.2 3.8 3.2 4 22 4 2.7 4 ATV71HU22Y
2.2 3 3 5.2 4.4 5.2 22 4.5 3.9 4.5 ATV71HU30Y
3 - 4 6.8 - 6.6 22 5.8 - 5.8 ATV71HU40Y
4 5 5.5 8.6 7.2 8.6 22 7.5 6.1 7.5 ATV71HU55Y
5.5 7.5 7.5 11.2 9.5 11.2 22 10 9 10 ATV71HU75Y
7.5 10 11 14.6 12.3 15.5 22 13.5 11 13.5 ATV71HD11Y
11 15 15 19.8 16.7 20.2 22 18.5 17 18.5 ATV71HD15Y
15 20 18.5 24 21 24 22 24 22 24 ATV71HD18Y
18.5 25 22 29 24 27 22 29 27 29 ATV71HD22Y
22 30 30 33 28 34 22 35 32 35 ATV71HD30Y
30 40 37 48 41 47 22 47 41 43 ATV71HD37Y
37 50 45 62 51 55 22 59 52 54 ATV71HD45Y
45 60 55 68 57 63 22 68 62 62 ATV71HD55Y
55 75 75 84 70.5 88 22 85 77 84 ATV71HD75Y
75 100 90 109 92 101 22 110 99 104 ATV71HD90Y