User`s manual
48
3. Setup for the communication option cards
Configuring communication monitoring
Since the Altivar 58’s communication monitoring time out is the same as the default value of the Altivar 71’s [Modbus time out] (ttO)
field (10 s), there is no point in modifying the value of this field.
Modification of these parameters will only take effect on the next power-up.
After transfer of the drive configuration by the PowerSuite software workshop, the
[Channel switching] (CHCF) parameter is
automatically assigned to
[8 serie] (SE8), thus providing access to memory mapping for the Altivar 58 compatible with the Altivar 71.
PLC configuration and application
The fact of opening the Altivar 71’s "ATV58(F) compatibility" memory zone (SE8 mode) means that no changes need to be made in the
PLC application.
However, in response to a function 43 identification request (16#2B) the drive will identify itself as an Altivar 71, not an Altivar 58(F).
Scenario 2 Using the built-in port when replacing the ATV58 terminal port
Configuring the drive
This example is implemented in the PowerSuite software workshop and consequently all the settings linked to the configuration parameters
(address, baud rate, parity) will be assigned automatically, identical to the Altivar 58.
Configuring communication monitoring
Since the Altivar 58’s communication monitoring time out is the same as the default value of the Altivar 71’s [Modbus time out] (ttO)
field (10 s), there is no point in modifying the value of this field.
Modification of these parameters will only take effect on the next power-up.
PLC configuration and application
The fact of opening the Altivar 71’s "ATV58(F) compatibility" memory zone (SE8 mode) means that no changes need to be made in the
PLC application.
However, in response to a function 43 identification request (16#2B) the drive will identify itself as an Altivar 71, not an Altivar 58(F).