User`s manual
22
2. Drive setup
2. 1. Installation
2. 1. 1. Use in High Torque (170% of Tn) for catalog numbers starting with ATV58H or ATV58F
The dimensions given in the following sections can be used to compare those of an Altivar 58(F) equipped with an option card and its
operator terminal with an Altivar 71 also equipped with an option card and operator terminal.
These tables only include examples where the Altivar 71 takes up more space than the Altivar 58, as well as the proposed solutions.
2. 1. 1. 1. Single phase supply 200…240 V for catalog numbers starting with ATV58H.
Single phase drives are used primarily for simple applications. For low power ratings, the ATV 71 dimensions are greater than those of
the ATV58.
Where installation creates serious difficulties, we recommend substituting the single phase ATV58 with the ATV31H.
Fixing centers
The substitution kits can use the same fixings as those for the Altivar 58.
Comparison of dimensions
(1) No problem if space is left between 2 drives. Width incompatible if the ATV58(F) drives are mounted side by side.
(2) This difference is easily made up by the space required for the drive wiring.
(3) The depth of enclosures is usually considerably greater than that of the products.
If the enclosure depth poses a problem, it is always possible to order an Altivar 71 with a Z at the end of the catalog number. Your drive will
be supplied without a graphic display terminal and will, therefore, be 23 mm slimmer, e.g., ATV 71H075N4Z.
Width (1) Height (2) Depth (3)
ATV58HU09M2 113 206 167
ATV 71H075M3 130 230 195
ATV58HU18M2 113 206 167
ATV 71HU15M3 130 230 195
ATV58HU29M2 150 230 184
ATV 71HU22M3 155 260 207
ATV58HU41M2 150 230 184
ATV 71HU30M3 155 260 207
ATV58HU72M2 175 286 184
ATV 71HU40M3 155 260 207
ATV58HU12M2 230 325 210
ATV 71HU75M3 210 295 233