Product manual

7 SNMP Polling of I/NET System Variables TAC Xenta 527-NPR, Product Manual
36 (42) Schneider Electric Buildings AB, Mar 2010
04-00053-01-en
7.1 SNMP System Variables
The following I/NET-related SNMP system variables are available for
polling:
Table 7.1: I/NET System Variables
System Variable Description
System.CpuLoad
(MIB object: inetLocalProcessorLoading)
The I/NET controller LAN (CLAN) loading (0-100%).
(The Xenta 527-NPR processor loading)
System.FreeMemory
(MIB object: inetFreeMemory)
The amount of free memory. (Number of free dynamic
RAM memory) (The Xenta free memory.)
System.NofResets
(MIB object: inetProcessorResets)
The number of resets. Cleared at restart Coldstart or
restart Reload. Retains its value during restart Warm-
start. (The number of Xenta resets.)
inet.snmp.freeIoPackets
(MIB object: inetFreeIOPackets)
The number of free packets.
(The number of IOPackets available to I/NET)
inet.snmp.messagesRouted
(MIB object: inetMessagesRouted)
The running message total for the target unit.
(The number of messages sent by I/NET)
inet.snmp.localCLANLoading
(MIB object: inetLocalCLANLoading)
The controller LAN loading on the Xenta
inet.snmp.averageResponseTime
(MIB object: inetAverageResponseTime)
The average response time on the I/NET network
inet.snmp.fastestResponseStation[0],..[63]
(MIB object: inetFastestResponseStation [0],..[9])
Address fastest station
inet.snmp.fastestResponseTime [0],..[63]
(MIB object: inetFastestResponseTime [0],..[9])
The (fastest) time for this station to respond
inet.snmp.slowestResponseStation[0],..[63]
(MIB object: InetSlowestResponseStation[0],..[9])
Address slowest station
inet.snmp.slowestResponseTime[0],..[63]
(MIB object: inetSlowestResponseTime[0],..[9])
The (slowest) time for this station to respond
inet.snmp.CLANLoading[0],..[63]
(MIB object: inetCLANLoading[0],..[63])
The controller LAN loading at this device.(0-100%)
inet.snmp.processorLoading[0],..[63]
(MIB object: inetProcessorLoading[0],..[63])