5 Setting Up I/NET Communications TAC Xenta 527-NPR, Product Manual
28 (42) Schneider Electric Buildings AB, Mar 2010
04-00053-01-en
10 Specify whether or not messages sent from the Xenta 527-NPR
should be I/NET 2000 compatible. If you are not using the Xenta
527-NPR with an I/NET 2000 system, answer No.
5.1.2 From a Web Browser
To define I/NET communication parameters from a web
browser
1 Display the Configuration Profile editor:
In the “I/NET” section of the menu page, click Configura-
tion Profile
as shown in the following figure.
Note
When configuring the Xenta 527-NPR from a web browser, be aware
that you will be unable to define the Encrypted UDP port number or
the Encryption Key. If you intend to use encryption, you will have to
make the necessary configuration adjustments to the Xenta 527-NPR
from a console window or from the NPR Configuration editor in
I/NET.