Datasheet

51
Zone Controllers
LonMark
®
certified individual room controllers for VAV applications (Variable
Air Volume) connected to an external air flow controller (Belimo VAV Com-
pact). The controller keeps a constant temperature in the zone by controlling
the air flow, optional heating stages, and fan in sequence. By using a carbon
dioxide sensor, the air quality can be controlled in the zone. The controller
can be operated stand-alone or within a LonWorks
®
network. PI control with
individual P-band and I-time setting for heating and cooling. Can be moni-
tored and parameters can be set centrally via the central system or remotely
with the TAC Xenta LonWorks
®
Operator Panel.
FUNCTIONAL FEATURES
Various applications:
Single-step control with
setpoint calculation of an
external air flow controller.
Two-step setting with cooling
and heating in sequence.
Heating operation via an
electric reheater or hot water.
Slave function mode of
operation and setpoint for
several slave controllers are
controlled by one master.
Setpoint adjustment via a wall
module with setpoint adjuster
or via a LonWorks
®
network
variable.
Seven modes of operation:
comfort, standby, bypass,
unoccupied, off, slave and
purge mode.
Air quality based adjustments.
Configurable limit values MIN
and MAX air flow limit.
Alarm monitoring high or
low room temperature, open
window, temperature sensor
error, etc.
Occupancy sensor, window
contact and cool-down
protection, CO
2
measurement
input.
SPECIFICATIONS
Operating voltage . . . . . . . . . . . . . . . . 24 V AC ±20%
Power consumption . . . . . . . . . . . . . . . 4 VA
Dimensions. . . . . . . . . . . . . . . . . . . . . . 127 x 126 x 50mm
(5” x 5” x 2”)
Ambient temperature
Operation . . . . . . . . . . . . . . . . . . . . . . 0°C to +50°C (32°F to 122°F)
Storage . . . . . . . . . . . . . . . . . . . . . . . . . –20°C to +50°C (4°F to 122°F)
Humidity . . . . . . . . . . . . . . . . . . . . . . . max. 90% RH non-condensing
Enclosure rating . . . . . . . . . . . . . . . . . . IP 30
Inputs and outputs
Window contact . . . . . . . . . . . . . . . . . . Digital input
Occupancy sensor . . . . . . . . . . . . . . . . Digital input
Air damper . . . . . . . . . . . . . . . . . . . . . . 0 – 10 VDC
Heating valve . . . . . . . . . . . . . . . . . . . . 2-point output
(102-EF); 0 - 10 VDC (102-VF)
Room temperature . . . . . . . . . . . . . . . . Thermistor input
Air flow . . . . . . . . . . . . . . . . . . . . . . . . 0 – 10 VDC
CO
2
sensor . . . . . . . . . . . . . . . . . . . . . . 0 – 10 VDC
Wall module . . . . . . . . . . . . . . . . . . . . . As selected
For further specifications, see technical data sheet.
DESCRIPTION
0-073-0531-0 TAC Xenta 102-B VAV Controller
0-073-0533-0 TAC Xenta 102-EF VAV Controller electrical reheat
0-073-0535-0 TAC Xenta 102-VF VAV Controller valve reheat
TAC Xenta 102-B, 102-EF,
102-VF VAV Controllers