Datasheet

44
TAC Xenta 491/492
Analog Output Module
For issuing analog actuating signals. The analog output module is only to be
used in combination with the TAC Xenta 300/401 basic controllers. The TAC
Xenta 492 is equipped with manual override switches for the analog outputs.
SPECIFICATIONS
Operating voltage . . . . . . . . . . . 24 V AC/ ±20%, 50/60 Hz, 19 - 40V DC
Power consumption . . . . . . . . . . max. 2 W
Dimensions incl. base . . . . . . . . 90 x 110 x 77mm (3.5” x 4.3” x 3”)
Protocol . . . . . . . . . . . . . . . . . . . FTT-10, LonTalk
®
Transmission rate . . . . . . . . . . . . 78 kbits/s
Ambient temperature
Storage . . . . . . . . . . . . . . . . . . . –20 °C to +50 °C (4 °F to +122 °F)
Operation . . . . . . . . . . . . . . . . . 0°C to +5C (+32°F to 122°F)
Humidity . . . . . . . . . . . . . . . . . . max. 90% RH non-condensing
Analog outputs
Quantity . . . . . . . . . . . . . . . . . . 8
Output signal . . . . . . . . . . . . . . 0 – 10 V DC
Manual switch . . . . . . . . . . . . . MAN, AUTO and Pot. 0 – 10V DC
(TAC Xenta 492)
For further specifications, see technical data sheet.
DESCRIPTION
0-073-0301-0 TAC Xenta 491 without manual switches
0-073-0303-0 TAC Xenta 492 with manual switches
0-073-0902-0 TAC Xenta 400 terminal part
Programmable Controllers
FUNCTIONAL FEATURES
Universal inputs provide
installation flexibility
Designed for TAC Vista and
open standard LonWorks
systems
Perfect for distributed
installations
Manual override switches
provide local bypass operation
Cost-effective installation and
maintenance using separate
terminal base and plug-in
electronic units
Individually configurable using
the TAC Menta programming
tool