Datasheet

37
A compact, freely programmable controller which is LonMark
®
certified and
has 20 fixed inputs and outputs. The controller can be expanded to up to 40
inputs/outputs using two expansion modules. It does not include peer-to-
peer or BMS communication. The controller can be upgraded at any time to
a networkable version without changing the hardware. The TAC Xenta OP
Operator Panel and a compatible terminal block are included in the stand-
alone package.
TAC Xenta 300 Stand Alone
SPECIFICATIONS
Operating voltage . . . . . . . . . . . . . . . . . 24 V AC/DC ±20%, 50/60 Hz
Power consumption . . . . . . . . . . . . . . . . max. 5 W
Data backup in event of power failure . . 72 h RAM-Backup
Ambient Temperature
Storage . . . . . . . . . . . . . . . . . . . . . . . . . –20 °C to +50 °C
(4 °F to +122 °F)
Operation . . . . . . . . . . . . . . . . . . . . . . . 0 °C to +50 °C
(+32 °F to +122 °F)
Humidity . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions incl. base . . . . . . . . . . . . . . . 180 x 110 x 77mm
(7” x 4.3” x 3”)
Protocol . . . . . . . . . . . . . . . . . . . . . . . . . FTT-10, LonTalk
®
Transmission rate . . . . . . . . . . . . . . . . . . 78 kbits/s
External LonWorks
®
data points
Input variable . . . . . . . . . . . . . . . . . . . . . max. 15 SNVTs
Output variable . . . . . . . . . . . . . . . . . . . max. 30 SNVTs
Interfaces
Serial connection . . . . . . . . . . . . . . . . . . RS232, RJ45 for PC or modem
(up to 9600 bit/s)
Operator panel . . . . . . . . . . . . . . . . . . . Modular jack, LonTalk
®
Protocol
For further specifications, see technical data sheet.
DESCRIPTION
0-073-0088 TAC Xenta 301/OP Stand Alone
0-073-0089 TAC Xenta 302/OP Stand Alone
0-008-7298 Upgrade TAC Xenta OP to N/P
ACCESSORIES
0-073-0901-0 Terminal part TAC Xenta 280/300
0-073-0920-0 TAC Xenta: Programming Serial Kit
Programmable Controllers
FUNCTIONAL FEATURES
Optimized for maximum flex-
ibility in HVAC control with on
board inputs and outputs
Fully programmable using the
intuitive TAC Menta program-
ming tool
Intelligent start time calcula-
tion minimizing energy usage
Available in a range of models
to secure cost-efficiency for
each application
I/O points can be extended by
TAC Xenta 400 I/O modules
Unit UI DI TI AO DO
TAC Xenta 301 4 4 4 2 6
TAC Xenta 302 4 4 4 4 4