AS-i Bus Class 8340 CONTENTS Schneider Electric Brands Description Page General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 TSXSAZ10 Master PLC Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 TSXSAY100 Master PLC Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 PLC Programming/Other Gateways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AS-i Bus General Information NTERFACE AS-i (Actuator Sensor Interface) is a bus made up of sensors and actuators with a very short response time. AS-i is an open industry standard supported by the AS-i association. The leading manufacturers of sensors, actuators, programmable controllers and connection accessories are members of this association. AS-i has the advantage of not being a sole supplier network.
AS-i Bus General Information Topology of the AS-i Bus The topology of the AS-i bus is unrestricted. The lack of restrictions enables the most direct connections to be made between the bus and the various sensors and actuators in an installation. The maximum length of the AS-i bus is 328 feet (100 m) (including main runs and tap-off runs). Cable runs of up to 984 feet (300 m) are possible using repeaters (signal regenerators).
AS-i Bus General Information AS-i Masters AS-i accepts different types of masters: • The programmable controller master module incorporating an AS-i communication port, directly transfers the data, transparently, to the PLC application program. The Premium PLC supports 1 to 8 AS-i masters; the Micro PLC supports 1 AS-i master. • The gateway master converts the AS-i bus from a simple communication node to a higher level bus.
AS-i Bus General Information AS-i Slaves An AS-i bus may be used with up to 31 slaves (each incorporating an ASIC) each consisting of 4 Input bits and 4 Output bits for cyclical exchange of information with the master, plus 4 parameter bits allowing extended functions (configuration, diagnostics, etc.). Each slave has its own address and a profile (defining the exchange of variables).
AS-i Bus General Information Example – Bus Supply Only 2 3 1 11 4 9 5 7 8 4 5 10 9 6 1 2 3 - + 0 5 6 8 5 12 13 7 5 1 2 3 TSXSAZ10 TSXSAY100 TSXSUPA0• or ABL6 XZSDE1113 + XZSDP 4 XZSDE11•3 + XZSDA••D•• 5 XZCG0•20 6 ABE8•••S••0 7 8 9 10 11 12 13 XS7C40AS101 or XS8C40AS101 XUJ••••••AS XALS200• XBLC5012•581 XZCB1•••1 XZCG0122 ATV58EU•••• 03/00 AS-i bus master for TSX Micro PLC’s or AS-i bus master for TSX Premium PLC Power supply unit for all sensors/actuators on the AS-i bus.
AS-i Bus General Information Example – Bus Supply plus Auxiliary Power Supply 12 14 13 13 2 3 1 4 5 6 7 10 12 8 9 11 1 XZCB1•••1 2 XZCB1•••2 3 XZSDE1113 + XZSDP 4 XZSDE1143 + XZSDA22D12 5 XZMA1 6 XZSDE1113 + XZSDA40D3 7 XZSDE1133 + XZSDP 8 XZCG012•D 9 XZCG0122 10 XZSDE2213 + XZSDP 11 XZCG0120•C 12 13 14 TSXSUPA0• or ABL6 Master Power supply unit, TSXSUPA05 8 Flat, unshielded, 2-core AS-i bus cable (yellow) with asymmetric profile, ensuring connection with the correct pol
AS-i Bus TSXSAZ10 Master PLC Interface MICRO AUTOMATION PLATFORM INTERFACE Introduction The TSXSAZ10 AS-i bus module enables the Micro PLC to act as the AS-i bus master. In this way up to 31 sensor/actuator type devices may be managed on the one AS-i bus. Up to 4 inputs and/or outputs can be connected to each device, giving a maximum of 248 I/O on one segment.
AS-i Bus TSXSAZ10 Master PLC Interface Module Diagnostics The Micro PLC centralized display block enables the display of the status of all the I/O channels, and the diagnostics for devices on the AS-i bus (present, missing, faulty, not conforming to the configuration): EXT BASE 64 16 0 4 R I/O 64 16 64 16 8 12 3 1 2 RUN 12 0 4 8 12 9 13 1 5 9 13 14 2 6 10 14 7 11 15 15 3 7 11 15 12 12 0 4 8 12 13 13 1 5 9 13 6 10 14 14 2 6 10 14 3 7 11 15 13 14 2 DIAG WRD 6 TER
AS-i Bus TSXSAZ10 Master PLC Interface Specifications Type of Module TSXSAZ10 Product Certifications AS-i No. 04601, NF C 63-850 AS-i Profile M2 Ambient Air Temperature Operation: +32 °F to +140 °F (0 °C to +60 °C), Storage: -13 °F to +158 °F (-25 °C to +70 °C) Degree of Protection IP 20 Vibration Resistance Conforming to IEC 68-2-6, Fc tests. Shock Resistance Conforming to IEC 68-2-27, EA tests.
AS-i Bus TSXSAY100 Master PLC Interface PREMIUM AUTOMATION PLATFORM INTERFACE Introduction The TSXSAY100 master module for the AS-i bus enables the Premium PLC to act as the AS-i bus master. In this way, up to 31 sensor/actuator type devices may be managed on one AS-i bus. Up to 4 inputs and/or outputs can be connected to each device, giving a maximum of 248 I/O on one segment.
AS-i Bus TSXSAY100 Master PLC Interface Module Diagnostics The TSXSAY100 module display unit displays the status of all the I/O channels (Slave mode) and is used for diagnostics of devices on the AS-i bus (Bus mode): Bus Mode Slave Mode (SLV) Displays the address of the selected Slave. Displays image of the AS-i bus; each LED 1 to 31 corresponds to a Slave address on the bus.
AS-i Bus PLC Programming/Other Gateways Software Setup The AS-i bus is configured using PL7 Micro/Junior/Pro software. The utilities available are based on the principle of simplicity: • Management of profile tables, parameters, and data by the master (this management is transparent to the user). • Topological I/O addressing: each AS-i slave declared on the bus is assigned a topological address on the bus by the user. This is transparent to the user.
AS-i Bus PLC Programming/Other Gateways Software Diagnostics Diagnostics performed using the centralized display unit on the Micro PLC or using the centralized display unit on the TSX SAY 100 module of the Premium PLC can be completed using an FTX517 terminal or PC compatible with PL7 Micro/Junior/Pro software. The terminal connected to the Micro/Premium PLC is used for operational diagnostics of the TSXSAZ10 and TSXSAY100 master modules, the AS-i bus and the slave devices on the AS-i bus.
AS-i Bus Repeater The repeater allows an AS-i link to be extended by 328 feet (100 m). The maximum length of the bus becomes 984 feet (300 m). The repeater is connected directly to the flat AS-i cable by insulation displacement connectors (IDCs). There is electrical insulation between the segments.
AS-i Bus Addressing Terminal The addressing terminal is used to set and change the addresses of AS-i slave devices. It is lightweight, hand-held, and powered by a rechargeable battery. A battery charger is included. Selection Description Catalog Number Addressing terminal Battery operated. Battery charger included. For addressing intelligent modules, splitter boxes and AS-i slaves. XZMC11US Connection cable adaptors Cable length: 0.
AS-i Bus Push Button Control Stations Selection Description Operator Colors Control stations with 2 spring return flush push buttons, Ø 22 mm Control stations with 2 spring return flush illuminated push buttons, Ø 22 mm ■ ■ Catalog Number Push button “I” (N/O contact): White Push button “O” (N/C contact): Black XALS2001 Push button “I” (N/O contact): Green Push button “O” (N/C contact): Red XALS2002 Push button 1 (N/O contact): Green Push button 2 (N/C contact): Red XALS2003 Illuminated push but
AS-i Bus Push Button Control Stations Environment Product Certifications AS-i No.
AS-i Bus 12-Button Keypads Selection Description Mounting Method 12-button keypads Marked 0 to 9, +, - (1) Flush mounting Catalog Number XBLC5012F581 Surface mounting XBLC5012R581 Dimensions 9 6 3 + (1) (2) (4) XBLC5012F581 1.16 29.5(1) 0.92 2.58 23.3 65.6 (3) (1) Connection by screw terminal plug-in block = = 2.33 +0.5 0 +0.02 2.83 59.2 0 72 (1) Spacers, solder lugs and nuts included (2) Alternative mounting using M3 screws, length 0.5 inches (12 mm), not included (3) 0.06 inches (1.
AS-i Bus 12-Button Keypads Specifications These dust and damp protected compact keypads incorporate tactile feedback and are particularly suited to the majority of industrial applications. The keypads are constructed using a single piece elastomer membrane, with the keys molded in, and the whole assembly is fixed to a mounting base plate (2 mounting methods: flush mounting or surface mounting).
AS-i Bus Inductive Proximity Sensors Sensors Flush Mountable in Metal Nominal sensing distance (Sn) 0.39 inches (10 mm) 0.59 inches (15 mm) 0.79 inches (20 mm) XS1M30AS101 XS7C40AS101 XS8C40AS101 Product Certifications AS-i No. 16901 AS-i No.
AS-i Bus Inductive Proximity Sensors Dimensions XS1 XS7, XS8 1.18 30 1.57 40 0.79 20 1.57 40 (1) 0.98 25 (4) 2.03 51.5 (2) (1) Cable, length 2.62 ft (0.8 m) 2.36 60 4.61 117 2.36 60 (1) 2xØ0.21 2xØ5.3 (3) = 0.63 0.94 16 1.61 24 41 Dual Dimensions: (1) Output or “flash” function LED (2) Alarm LED inches mm 1.18 1.57 30 40 = (3) 1 tapped entry for No. 13 plastic cable gland (4) 2 elongated holes 0.21 x 0.28 in (5.
AS-i Bus Photoelectric Sensors Type of Unit Back Cover ■ Complete Detectors 1 2 System Thru-beam 1 Polarized reflex 2 Diffuse with background suppression 1 Type of Transmission Infra-red Red Infra-red Nominal Sensing Distance (Sn) 49.2 ft (15 m) 19.7 ft (6 m) ▲ 2.3 ft (0.7 m) 3.94 ft (1.2 m) – XUJK103534AS ● XUJK063539AS XUJK703538AS XUJK123538AS XUJZAS1 – – Selection Catalog Number Specifications Product Certifications AS-i No.
AS-i Bus Photoelectric Sensors Dimensions Detection Curves Thru-beam system ∅ of beam cm 10 6 2 59 ft 18 m -6 -10 Sn Sn Diffuse system (side approach recommended ∅ of beam cm ∅ of beam cm 10 6 4 2 0 -2 -4 -6 Ø 0.79 Ø 20 0 -2 Polarized reflex system 2 0 -2 26 ft 8 m 49 ft 15 m 0.16 ft 2.3 ft 3.94 ft 0.05 m 0.7 m 1.2 m -6 -10 Sn 20 ft Sn 6 m Sn Sn 2.3 ft 0.7 m Sn 3.94 ft Sn 1.
AS-i Bus Illuminated Indicator Banks Illuminated indicator banks are visual or audible signalling units used mainly to indicate machine operation sequences and to check status from a distance. The illuminated units are visible throughout 360°. Examples: machine stop - start, no material, call technical staff, fault indication, etc. Supplied as sub-assemblies for user assembly of up to 4 units (illuminated or audible).
AS-i Bus Illuminated Indicator Banks Audible Signalling Units Description Signal Audible signalling units, 90 db at 3.
AS-i Bus Illuminated Indicator Banks DIMENSIONS Illuminated indicator banks without high intensity “flash” lamps with high intensity “flash” lamp (4) Dual Dimensions: (4) inches mm b (1) (5) (4) (3) b (3) (2) (1) = = 1.65 42 Ø 2.68 68 Number of illuminated or audible signalling units (3) 1 2 3 4 (1) XVAC21 (2) XVAS102 b 6.26 in (159 mm) 8.31 in (211 mm) 10.35 in (263 mm) 12.
AS-i Bus Variable Drive Controllers for Asynchronous Motors ATV58HU.tif ALTIVAR® 58 DRIVE CONTROLLER INTERFACE Description The TELEMECANIQUE® ALTIVAR 58 drive controller range is used to control asynchronous electrical motors with a power of 0.37 to 15 kW for 200/240 Vac single-phase and 200/240 Vac – 380/500 Vac 3-phase power supply voltages.
AS-i Bus Variable Drive Controllers for Asynchronous Motors ALTIVAR 58 Drive Controller Functions Start-Stop Commands via the AS-i Bus The AS-i bus communication card is used to perform the following commands: • Forward operation • Reverse operation • Normal stop on deceleration ramp • Fast stop • DC injection stop • Freewheel stop • Reset faults (for drive controller reset) Speed Commands via the AS-i Bus One of the following operating modes can be selected: • 2 directions with 4 preset speeds • 1 directio
AS-i Bus Variable Drive Controllers for Asynchronous Motors Communication Card Description AS-i card Connector For Drive Controllers Catalog Number Removable terminals ATV 58 all ratings VW3A58305 Length Catalog Number 6.
AS-i Bus Variable Drive Controllers for Asynchronous Motors Specifications Product Certification Ambient Air Temperature AS-i Pending Operation +14 °F to +104 °F (-10 °C to +40 °C) Storage -13 °F to +149 °F (-25 °C to +65 °C) UL Listed E164874 CCN NMMS CSA Certified LR96921 Class 3211 06 Compliance Standards Electrical Specifications Current Consumed On the AS-i bus 30 mA Communication Specifications (parameter entry by default, factory setup) Profile 7.
AS-i Bus XALSZ1 (Spider) and ZB2BZ Interface Boards Adaptors for Control and Signalling Units Description Signalling Mode of Illuminated Indicator Interface-2 inputs/2 outputs Inputs for digital contacts Outputs for 24 Vdc LEDs DL1CJ024• ■ Steady Interface-4 inputs/4 outputs for printed circuits Inputs for digital contacts Outputs for indicators ■ Mounting Position Catalog Number - XALSZ1 Steady Steady or flashing depending on parametering Vertical ZB2BZS2V Horizontal ZB2BZS2H Vertical ZB2BZ
AS-i Bus XALSZ1 (Spider) and ZB2BZ Interface Boards Specifications for AS-i Adaptor, XALSZ1 Ambient Air Temperature Operation: -13 °F to +158 °F (-25 °C to + 70 °C) Storage: -40 °F to +158 °F (-40 °C to + 70 °C) Degree of Protection IP 20 Connection By 2 wires, each 4 x 22 AWG (4 x 0.
AS-i Bus TELEFAST SB2 Intelligent Interfaces Description The TELEFAST® SB2 AS-i intelligent interfaces are based upon the TELEFAST 2 concept. They allow standard discrete sensor and actuator devices to be connected to the AS-i bus. They are available in 4 or 8 I/O versions. Their inputs, depending upon the model, may be isolated from the AS-i bus. Their outputs (either solid state or electromechanical relay) may be used to control actuators of 1 to 5 A.
AS-i Bus TELEFAST SB2 Intelligent Interfaces 201 301 204 105 205 206 No. of Channels Function Input 4 Output Input 4 – Bus – – 4 relays 1 N.O. – 125 Vdc/ 250 Vac 2 solid state 2 ABE8S40SB00 8 4 solid state 4 4 relays 1 N.O. Q4 Q1 1 4 104 4 108 105 206 201 204 Voltage 205 301 ABE8R44S•• 24 Vdc ext.
AS-i Bus TELEFAST SB2 Intelligent Interfaces General System Environment Product Certifications AS-i Enclosure Rating Conforming to IEC 529 IP 2X Shock Resistance Conforming to IEC 68-2-27 11 ms (semi-sinusoidal) 15 g (acceleration) 5 to 13.2 Hz ± 1 mm 13.2 to 100 Hz- 0.
AS-i Bus TELEFAST SB2 Intelligent Interfaces 4-Channel Modules Type of Interface ABE8S40SB00 ABE8R04S010 ABE8S22SBB1 Function 4 inputs 4 outputs 2 inputs/2 solid state outputs AS-i Certification No. 113 No. 112 No.
AS-i Bus TELEFAST SB2 Intelligent Interfaces 8-Channel Modules Type of Interface ABE8S44SBB0 ABE8S44SBB1 ABE8R44SB11 ABE8R44SF10 Function 4 inputs/4 solid state outputs 4 inputs/4 solid state outputs 4 inputs/4 EM relay outputs 4 inputs/4 EM relay outputs AS-i Certification No. 114 No. 179 No. 23501 No. 23401 Supply voltage Ext.: 19.2 to 30 Vdc From the bus From the bus Ext.
AS-i Bus TELEFAST SB2 Intelligent Interfaces ABE8S40SB00 ABE8R04S010 Bus + – +/ 114 104 214 113 204 103 213 (3) –/ u1 u2 –/ +/ Channel 1 ABE8S44SBB0 Q4 u1 (2) Channel 2 112 102 Q3 202 101 211 4 201 3 2 1 114 104 214 113 204 103 +/ – + Channel 1 I4 213 112 203 102 I3 212 202 211 201 7 111 I2 101 I1 Q2 111 Q1 –/ 203 + – – + (1) 212 Bus Channel 2 ABE8S44SBB1 Bus a 24 V (2) Q4 108 Q1 208 204 104 I4 205 101 4 201 7 + ABE-7BV10 – 105 I1 2
AS-i Bus TELEFAST SB2 Intelligent Interfaces Using TELEFAST® SB2 Intelligent Interfaces with Motor Starters Recommended Wiring Diagrams AS-i – AS-i – AS-i + AS-i + + – Ι+ Ι– I2 I1 I3 I4 O2 O1 O3 O4 108 208 107 207 106 206 105 205 104 204 103 203 102 202 101 201 4 3 7 2 5 ABE8S44SBB1 6 1 24 V – AU – KM1 0V – KM3 – KM4 – Q1 – Q2 – Q3 – Q2 – Q3 – KM2 – Q4 5/L3 – KM4 3/L2 – KM3 – Q4 2/T1 4/T2 6/T3 2/T1 4/T2 6/T3 2/T1 4/T2 6/T3 2/T1 4/T2 6/T3 W U V W U
AS-i Bus TELEFAST SB2 Intelligent Interfaces Using TELEFAST® SB2 Intelligent Interfaces with Reversing Motor Starters Recommended Wiring Diagrams AS-i – AS-i – AS-i + AS-i + + – Ι+ Ι– I2 I1 I3 I4 O2 O1 O3 O4 108 208 107 207 106 206 105 104 205 204 103 203 102 202 101 201 4 7 3 2 5 ABE8S44SBB1 6 1 24 V –Q –AU – KM1 0V – KM2 – KM2 – KM1 + 24 V – KM1 0V – KM2 5/L3 3/L2 safety interlock 1/L1 + 24 V –Q 6/T3 4/T2 V W 2/T1 – KM2 U – KM1 M Data Exchange Specification
AS-i Bus TELEFAST SB2 Intelligent Interfaces Using TELEFAST® SB2 Intelligent Interfaces with Motor Starters Associated Components Standard Motor Starters Rated Operational Power for Utilization Category AC-3 400/415 Vac kW ◆ 220/230 Vac kW DOL Non-reversing Starters Disconnect/ Protector Catalog No. Add-on Auxiliary Block Catalog No. Contactors KM1 to KM4 Catalog No. Reversing Starters Disconnect/ Protector Catalog No. Add-on Auxiliary Block Catalog No. Reversing Contactors KM1 & KM2 Catalog No.
AS-i Bus Intelligent Splitter Modules Passive Intelligent 4-way XZSDP40D1 XZSDP40D1 XZSDP40D1 XZSDA40D3 XZSDA40D3 XZSDA40D3 4 Inputs 2 Inputs/ 2 Outputs XZSDA22D32 XZSDA22D32 + XZSG10 4 Outputs XZSDA04D32 XZSDA04D32 + XZSG10 Connection Bases XZSDE1113 XZSDE1133 XZSDE2213 XZSDE2323 44 © 2000 Schneider Electric All Rights Reserved XZSDE2213 XZSDE2323 03/00
AS-i Bus Intelligent Splitter Modules 4-Port Intelligent Splitter Modules for Connections to Actuators ■ or Sensors ▲ XZSDA22D32 XZSDA40D3 Description Sensor Supply Separate Supply to the Actuators Splitter module 2 inputs/ 2 solid-state outputs Via XZSDE•••• connection base, from the AS-i bus Via XZSDE•••• connection base Splitter module 4 inputs (200 mA max.
AS-i Bus Intelligent Splitter Modules Specifications 2 inputs/2 outputs 4 inputs/4 outputs 4 inputs/4 outputs XZSDA22D32 XZSCA44D21 XZSCA44D22 Product certifications AS-i No. 10201 AS-i No. 26201 Ambient Air Temperature Operation: -13 °F to +158 °F (-25 °C to +70 °C) Storage: -40 °F to +185 °F (-40 °C to +85 °C) Degree of Protection IP 67 Type Environment Materials Connection AS-i No.
AS-i Bus Intelligent Splitter Modules 4 inputs 4 outputs XZSDA40D3 XZSDA04D32 Product Certifications AS-i No. 03602 AS-i No.
AS-i Bus Cabling and Connection Accessories Passive Splitter Modules for Connections to AS-i Sensors or Actuators Description Catalog Number Splitter module, 4-way (2 A max. per way) XZSDP40D1 XZSDP40D1 Accessories for Connection of AS-i Flat Cable Tap-Offs Connection to flat cables by IDC (Insulation Displacement Connector). Ue - 40 V, Ie - 2 A. Degree of protection IP 40.
AS-i Bus Cabling and Connection Accessories Flat Cables and Accessories The special profile of these 2-core flat cables eliminates the risk of polarity reversal when connecting. Connection to the cables are made by IDCs (see connection accessories). The sheath material self-seals the holes made by the IDC in the event of the connector being removed. Degree of protection IP 67.
AS-i Bus Cabling and Connection Accessories Dimensions Splitter modules XZSDA•••, XZSDP40D1 Connection bases XZSDE11•3 Connection bases XZSDE2••• 0.79 20 3.15 80 0.78 1.22 20 31 1.77 (2) 45 (2) (3) 4 holes for mounting PG11 cable gland or blanking plug. (4) PG11 cable gland. 2.60 66 BU – 0.16 4 3.15 80 0.02 0.5 0.10 2.5 0.14 BN 0.26 3.6 6.5 + 1.22 1.77 31 45 0.5 13 Dual Dimensions: Splitter boxes XZSCA44D21 XZSCA44D22 0-2 I-1 0-1 1.06 27 I-2 1.
AS-i Bus Cabling and Connection Accessories Dimensions T-connectors XZCG0120 1.97 50 0.59 15 1.2 30.4 0.59 15 1.21 30.7 XZCG0220 1.18 30 0.79 20 0.79 20 (1) 0.39 10 (1) Dual Dimensions: XZCG014•• 0.71 18 1.87 47.5 0.11 2.7 0.17 4.3 1.54 39 0.17 4.3 0.31 8 0.11 2.7 0.68 17.3 0.59 15 (1) 0.63 16 0.47 12 (1) 0.09 2.3 1.3 33 Connector adjustable to 2 positions through 90° 0.83 21 Tap-Offs XZCG012•• 0.6 15.3 (1) 0.43 10.8 0.01 0.
AS-i Bus Extension Cables Extension Cables XZCR••••A• Connections 4 AS-i Sensors or Actuators 3 1 5 XZCR••••E• 3 4 4 3 4 3 5 2 1 4 3 5 1 52 1 2 3 2 2 1 3 4 5 2 1 XZCR••••C• 3 4 1 2 3 5 XZCR••••D• 5 2 1 4 3 1 2 1 4 1 2 3 4 5 1 2 3 4 5 3 2 1 1 2 3 4 1 2 3 4 3 4 5 5 2 • Proximity sensors XS1 • Photo-electric detectors XUJ • Control stations XAL • Proximity sensors XS1 • Photo-electric detectors XUJ • Control stations XAL • Proximity sensors XS1 • Photo-elect
AS-i Bus Extension Cables Extension Cables Standard Sensors 4 XZCR••••B• 3 5 2 1 XZCR••••F• 4 3 1 2 1 2 3 5 5 2 Limit switches XCKJ•••D and XCM (4 or 5-pin) N.O. contact only. • Photo-electric detectors, 3-wire PNP, Osiris design 18, and Osiris design compact XUL. Operation: “light on” only. • Photo-electric detectors, 3-wire PNP, XUB. - thru beam and reflex: operation: “light on” only - diffuse: operation: “dark on” only. • Limit switches XS••••••D, type PNP 3-wire. N.O. output only.
AS-i Bus Extension Cables Extension Cables with M12 Male/Female for Terminal Connections, 8 mm Diameter Female Connectors Male Connector Type M12, 2-pin, straight M12, 3-pin, straight Female Connector Type For terminal connections Ø 8 mm, 3-pin, straight Application See extension cable selection guide according to type of device to be connected to the AS-i bus, pages 52 and 53. Ø 8 mm, 3-pin, elbowed Selection PvR Cable, Color Black L = 1.64 ft (0.5 m) XZMG11 – – L = 3.
AS-i Bus Extension Cables Extension Cables with M12 Male Connector and M8 Female Connector Male Connector Type M12, 3-pin, straight Female Connector Type M8, 3-pin, straight Application See extension cable selection guide according to type of device to be connected to the AS-i bus, pages 52 and 53. M12, 4-pin, straight M8, 3-pin, elbowed M8, 4-pin, straight M8, 4-pin, elbowed Selection PvR Cable, Color Black L = 3.28 ft (1 m) XZCR1509040H1 XZCR1510040H1 XZCR1509041J1 XZCR1510041J1 L = 6.
AS-i Bus Extension Cables Extension Cables with M12 Male Connector and M12 Female Connector Male Connector Type M12, 3-pin, straight Female Connector Type M12, 3-pin, straight Application See extension cable selection guide according to type of device to be connected to the AS-i bus, pages 52 and 53. M12, 3-pin, elbowed M12, 3-pin, straight M12, 3-pin, elbowed Selection PvR Cable, Color Black L = 3.28 ft (1 m) XZCR1511040A1 XZCR1512040A1 XZCR1511040E1 XZCR1512040E1 L = 6.
AS-i Bus Extension Cables Extension Cables with M12 Male Connector and M12 Female Connector Male Connector Type M12, 5-pin, straight Female Connector Type M12, 5-pin, straight Application See extension cable selection guide according to type of device to be connected to the AS-i bus, pages 52 and 53. M12, 4-pin, straight M12, 5-pin, elbowed M12, 3-pin, straight M12, 4-pin, straight M12, 4-pin, elbowed M12, 3-pin, straight M12, 3-pin, elbowed Selection PvR Cable, Color Black L = 3.
AS-i Bus Extension Cables Extension Cables with M12 Male Connector and M12 Female or DIN 43650 A Connectors Male Connector Type M12, 3-pin, straight Female Connector Type M12, 3-pin, straight Application See extension cable selection guide according to type of device to be connected to the AS-i bus, pages 52 and 53. M12, 3-pin, elbowed DIN 43650 A, elbowed Selection PvR Cable, Color Black L = 3.28 ft (1 m) XZCR1511062F1 XZCR1512062F1 XZCR1523062K1 L = 6.
AS-i Bus Extension Cables M12 Male Connectors and Extension Cables, M12 Two-Way Splitter Boxes Male Connector Type M12, 4-pin, straight Application See extension cable selection guide according to type of device to be connected to the AS-i bus, pages 52 and 53. M12, 5-pin, straight Selection Connection to Cable by Screw Terminal Connections PvR Cable, Color Black XZCC12MDM40B XZCC12MCM40B – – L = 1.64 ft (0.5 m) – – XZCP1564L05 – L = 3.28 ft (1 m) – – XZCP1564L1 – L = 6.
AS-i Bus Power Supply Module and Unit Description The TSXSUPA02 power supply module and the TSXSUPA05 power supply unit integrate the special filters required to supply an AS-i bus. These parts ensure the polarization of the AS-i bus as well as the power supply for sensors connected to it (within t he limits of the available power). The TSXSUPA05 unit also has a 24 Vdc output designed to supply other items (PLCs, sensors, pre-actuators, etc.) whether or not they are connected to the AS-i bus.
AS-i Bus Power Supply Module and Unit Specifications Type of Power Supply Module TSXSUPA02 Nominal Primary Voltage 100 to 120 Vac 200 to 240 Vac 100 to 120 Vac 200 to 240 Vac Primary Voltage Range 85 to 132 Vac 170 to 264 Vac 85 to 132 Vac 170 to 264 Vac Network Limit Frequency 47 to 63 47 to 63 47 to 63 47 to 63 Max. Immunity Time to Microbreaks 10 ms 10 ms 10 ms 10 ms Secondary Nominal Voltages 30 V (AS-i bus) 30 V (AS-i bus) 24 V (process) Voltage Limits 29.5 to 31.6 V 29.
AS-i Bus Insulation Control Relay for AS-i Bus General The RM0PAS101 insulation control relay detects and signals any ground fault on either of the 2 polarities of an AS-i bus cable. It takes into account any input/output ground faults of PNP intelligent splitter boxes (not isolated from the bus). 1 Q4 108 Q1 2 3 TEST RESET BUS BUS 201 1 101 301 4 104 204 105 205 5 6 Operating Principle 206 OK 4 + FAULT 7 FAULT 7 Insulation control relay for AS-i bus: 1. 2. 3. 4. 5. 6. 7.
AS-i Bus Insulation Control Relay for AS-i Bus • Test The relay has a test feature to simulate faults. Each test sequence alternatively simulates an insulation fault on one of the two AS-i bus polarities. The relay must respond as if the fault was authentic and following each test, the relay must be reset as detailed above. Each subsequent test sequence checks the other polarity of the AS-i bus (see function diagram on next page). Two methods of testing are possible: • Locally, by pressing the TEST button.
AS-i Bus Insulation Control Relay for AS-i Bus Selection Description Catalog Number Insulation control relay for AS-i bus (supplied with an impedance adaptor) RM0PAS101 Impedance adaptor (replacement part) LA9RM401 2.99 76 1.38 35 2.28 58 Dimensions 0.59 15 2.28 58 2.64 67 3.
AS-i Bus Insulation Control Relay for AS-i Bus Specifications Environment Product Certification AS-i No.
AS-i Bus Product Index by Description Description Catalog Number Description Catalog Number 12 Button Keypad XBLC5012•••• 20 Jumper Cable XZCR15••••••• 52-58 XALSZ1 33 2 I+ 2 O Module for Operator Station Keypads XBLC5012•••• 20 2 Push Buttons Operator Station XALS20•• 18 M12, 5 pin, Straight, Extension Cable XZCP••••••• 59 8-Port Splitter Box XZSCA••••• 45 Male Connector Plug XZCC12M••••• 59 Addressing Terminal XZMC11US 17 Master for TSX Micro PLC TSXSAZ10 9 Addressing Te
AS-i Bus Product Index by Catalog Number Catalog Number Description ABE7••••• TELEFAST 2 Accessories 36 ABE8••••• TELEFAST 2 for AS-i 36 AR1SB3 Adhesive Label Holder 36 DL1B•••• Incandescent Bulb for XVA 27 LA9RM401 Impedance Adapter 64 RMOPAS101 Ground Leakage Relay 64 TSXDM3713E TSX 37 Micro PLC User Manual TSXSAY100 Master for TSX Premium PLC TSXSAZ10 Master for TSX Micro PLC 9 TSXSUPA•• Power Supply for AS-i Bus 61 VW3A58305 Altivar 58 Drive Controller AS-i Card 31 XALS
Square D Company 8001 Highway 64 East Knightdale, NC 27545 USA 1-888-SquareD (1-888-778-2733) www.squared.com Schneider Canada Inc. 19 Waterman Avenue, M4B 1 Y2 Toronto, Ontario (416) 752-8020 www.schneider.ca Catalog No. 8340CT0001 March 2000. D-Fax™ No.