Datasheet

Product data sheet
Characteristics
RSB2A080BDS
interface plug-in relay - Zelio RSB - 2 C/O - 24
V DC - 8 A - with socket
Main
Range of product Zelio Relay
Series name Interface relay
Product or component-
type
Plug-in relay
Device short name RSB
Contacts type and com-
position
2 C/O
Contact operation Standard
[Uc] control circuit volt-
age
24 V DC
[Ithe] conventional en-
closed thermal current
8 A at -40...40 °C
Status LED Without
Control type Without push-button
Sale per indivisible-
quantity
10
Complementary
Shape of pin Flat
Average resistance 1440 Ohm (DC) at 20 °C +/- 10 %
[Ue] rated operational voltage 19.2...26.4 V DC
[Ui] rated insulation voltage 400 V conforming to EN/IEC 60947
[Uimp] rated impulse withstand voltage 3.6 kV conforming to IEC 61000-4-5
Contacts material Silver alloy (Ag/Ni)
[Ie] rated operational current 4 A, NC (AC-1/DC-1) conforming to IEC
8 A, NO (AC-1/DC-1) conforming to IEC
Minimum switching current 5 mA
Maximum switching voltage 300 V DC
400 V AC
Switching voltage 5 V
Maximum switching capacity 2000 VA (AC)
224 W (DC)
Load current 8 A at 250 V AC
8 A at 28 V DC
Minimum switching capacity 300 mW at 5 mA
Operating rate <= 600 cycles/hour under load
<= 72000 cycles/hour no-load
Mechanical durability 30000000 cycles
Electrical durability 100000 cycles (8 A at 250 V, AC-1) NO
100000 cycles (4 A at 250 V, AC-1) NC
Operating time 4 ms between coil de-energisation and making of the Off-delay contact
9 ms between coil energisation and making of the On-delay contact
Marking CE
Average coil consumption 0.45 W DC
Drop-out voltage threshold >= 0.1 Uc DC
Safety reliability data B10d = 100000
Protection category RT I
Operating position Any position
Device presentation Complete product
Compatibility code RSB
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Jun 18, 2018
1

Summary of content (2 pages)