Daim Ntawv Qhia Tus Neeg Siv
Settings with Schneider Charge Controllers
Parameter Setting for Pytes Batteries with Schneider XW+&XW Pro MPPT 60/80
Advanced Setting > Charger Setting
Battery Type
Custom
Custom Setting
Charge Mode
3 Stage
Eqlz Mode
Disabled
Bulk Voltage
56.2 V
Absorb Voltage
56.2 V
Absorb Time
60 minutes
Float Voltage
55.8 V
Battery Temperature Compensation
0mV/C
Battery Capacity
100Ah per battery
Max Charge Rate Percentage
50 A per battery
Divide by total CC amp output
Charge Cycle
Warm
Recharge Volts
53 V
Absorb Time
1 Hour
Default Battery Temperature
Warm
Battery Voltage (Auto-detected)
51.2 V
Note: The charge controllers can be set to a 3 stage charging cycle, but the inverter should
be kept in a 2 stage charging cycle. Doing so, as well as setting the charge controller
recharge voltage to be greater than that of the inverter recharge voltage, will prioritize
charge controller charging over the inverter charging. Inverter charging is a grid/generator
charge which has a lower priority than solar charge controller charging.
Please refer to XW Pro Commissioning Guide - Schneider Electric Solar for more
information.