All Open Loop Settings are programmable with a SCP, Insight Local or/and Insight Cloud.
Disregard the communication cable that would go from battery to inverter.
Settings for Pytes Batteries with Schneider Inverters
Charger Setting > Custom Setting
Battery Type
Custom
Charge Cycle
2StgNoFloat
Bulk Voltage
56 V
Max Bulk Current
50A per battery
Max Discharge Current
50A per battery
Battery Capacity
100 Ah per battery
Max Charge Rate Percentage (%)
50A per battery
Divided by Total Inverter DC Amps*
Default Battery Temperature
Warm
Recharge Volts
51.2 V
Grid Support Volts
53 V
Absorb Volts
56 V
Absorb Time
1 hour
Charge Block Start
Default
Charge Block Stop
Default
Advanced Setting > Inverter Settings
Low Battery Cut Out Voltage
47 V
LBCO Hysteresis
2.0 V
LBCO Delay
5 Sec
High Battery Cut Out Voltage
56.5 V
Search Watts
Default
Search Delay
Default