Specifications
432E2230.fm/3
Schneider Electric
11 mars 2002
Functions and
characteristics
Power-monitoring unit
(cont.)
Power Meter Series 600
(cont.)
E58796
Electrical characteristics
Type of measurement True rms up to the 31st harmonic
On three-phase (3P, 3P+N)
Measurement current and voltage 0.25 % of reading
accuracy power 0.5 % of reading
frequency 0.02 Hz
power factor 1 % of reading
Data update rate 1 s
Input-voltage
characteristics
measured voltage 0 to 600 V AC (direct)
0 to 1000 kV AC (with external PT)
permissible overload 1.2 Un
frequency measurement range 45 to 66 Hz
Input-current
characteristics
CT rating adjustable from 5 A to 10 000 A
1
2-line liquid crystal display.
2
Up/down arrows.
3
Contrast button to adjust the display contrast.
4
Button used to scroll through available modes.
5
Button used to select modes and setup, resets and
diagnostics values.
secondary 1 A or 5 A
measurement range 0.004 to 1.2 In
permissible overload 500 A, 1 s
load 0.15 VA
Power supply AC version 90 to 600 V AC (± 10%), 30 VA
DC version 100/300 V DC (± 10%), 6 W
Pulse output Static output (96 mA at 240 V AC)
Mechanical characteristics
Weight 0.7 kg
IP Degree of protection (IEC 60529) IP52 front face, IP30 rest of case
Dimensions 114 x 114 x 154 mm
Environmental conditions
Operating temperature 0 °C to + 60 °C
Storage temperature - 20 °C to 70 °C
Humidity rating
5 to 95 % RH at 30
°C
Pollution degree
2
Installation category
II
Dielectric withstand
As
p
er EN 61010-1
Electromagnetic
compatibility
immunity to electrostatic
discharges
Level III (IEC 61000-4-2)
immunity to radiated fields Level III (IEC 61000-4-3)
immunity to fast transients Level II (IEC 61000-4-4)
conducted and radiated
emissions
CE (class A)
Safety
Europe CE, as per IEC 61010
Communication
RS485 port 2/4-wire, up to 38 400 bauds,
Modbus/Jbus and PowerLogic
Display characteristics
Type Back lit LCD