Specifications

6
Product selection guide
Panorama of the PowerLogic
range
Current transformers Panel instruments
TI Name AMP / VLT AMP / VLT
current transformer
Function
ammeter, voltmeter ammeter, voltmeter
Technology
analog digital
Installation
b cable connections
b insulated cable,
diameter 21 to 35 mm,
through transformer
b busbar through transformer:
v Prisma vertical busbars,
20 x 5 and 32 x 5 mm
v insulated flexible busbars,
30 x 10 to 65 x 32 mm
v Linergy busbars,
800 A and 1600 A
v rigid busbars,
20 x 5 to 55 x 165 mm
Installation
DIN rail
4 x 18 mm modules
DIN rail
2 x 18 mm modules
Applications
Installation monitoring
Panel instrumentation I / U I / U
Remote monitoring
Advanced remote monitoring
Sub-billing and cost allocation
Energy consumption
Consumption for different time periods
Consumption of other utilities
Optimisation of power contract and load curves
Power quality analysis
Monitoring of harmonics (THD)
Analysis of individual harmonic content
Detection of voltage sags and swells
Detection of transients
EN50160 compliance checking
Characteristics Characteristics
b transformation ratio:
40/5 A to 6000/5 A
b accuracy: class 0.5 to 3
b maximum rated operational voltage:
720 V AC
b standard or tropicalised
Measurement accuracy class 1.5 ± 0.5% ± 1 digit
Voltage measurement VLT:
500 V AC direct
or external VT
VLT:
600 V AC direct
or external VT
Current measurement AMP:
30 A direct
or external CT
AMP:
10 A direct
or external CT
Communication ports
Inputs / Outputs
Memory capacity
page XXX page XXX page XXX