Specifications

PowerLogic:
Circuit monitor series 4000
46
Input/output blocks may be added to the circuit monitor to:
Monitor the electrical installation, notably the status of the circuit breakers, and
check discrimination between protection devices
Measure the consumption of other commodities by counting the pulses sent
by water or gas meters
Measure the temperature of the transformers
Transmit parameters over analogue channels to other systems
The circuit monitor may be equipped with a total of 25 optional digital or analogue
input/outputs.
These input/outputs may be added in two different manners:
Either using an IOC44 card
Or the IOX input/output extender module and individual input/output modules
that connect to the extender
All these options may be installed in the field. Status changes on the digital inputs
are time-stamped to within the millisecond.
IOC44 card
This is an input/output card equipped with:
4 digital inputs 20 - 138 V AC/DC
4 digital outputs, including 3 relay outputs and a static output that may be
programmed as a pulse output. It may be installed in the option card slots of
the circuit monitor
There are three possible configurations for the
circuit monitor series 4000:
1 IOC44 card
2 IOC44 cards
1 IOC44 card and 1 ethernet ECC21 card
Description Part number
IOC44 card IOC44