Specifications
PowerLogic:
Circuit monitor series 4000
46
Input/output blocks may be added to the circuit monitor to:
■ Monitor the electrical installation, notably the status of the circuit breakers, and
check discrimination between protection devices
■ Measure the consumption of other commodities by counting the pulses sent
by water or gas meters
■ Measure the temperature of the transformers
■ Transmit parameters over analogue channels to other systems
The circuit monitor may be equipped with a total of 25 optional digital or analogue
input/outputs.
These input/outputs may be added in two different manners:
■ Either using an IOC44 card
■ Or the IOX input/output extender module and individual input/output modules
that connect to the extender
All these options may be installed in the field. Status changes on the digital inputs
are time-stamped to within the millisecond.
IOC44 card
This is an input/output card equipped with:
■ 4 digital inputs 20 - 138 V AC/DC
■ 4 digital outputs, including 3 relay outputs and a static output that may be
programmed as a pulse output. It may be installed in the option card slots of
the circuit monitor
There are three possible configurations for the
circuit monitor series 4000:
■ 1 IOC44 card
■ 2 IOC44 cards
■ 1 IOC44 card and 1 ethernet ECC21 card
Description Part number
IOC44 card IOC44