Specifications
PowerLogic:
Circuit monitor series 3000
38
Ethernet ECC21 card with HTML server (optional)
(2)
Copper ethernet link 10/100 BaseTX, RJ45 connector, 100-metre link
Fibre-optic ethernet link 100 Base FX, LC duplex connector, 1300 nm,
FO multimode with gradient index 62.5/125 µm
or 50/125 µm, 2000-metre link
Protocol Modbus/TCP/IP
Gateway function for products Master Modbus port, 31 daisy-chained slaves, 63 with repeater,
connected to the ECC21 2/4 wires, 1200 to 38400 bauds, also compatible with the
PowerLogic protocol
HTML server 1 standard page, 5 customisable pages
Firmware characteristics
14 data logs Up to 96 different parameters, factory-set logs ready to use
One 100 ms data log Parameters recorded every 100 ms for events (CM3350 only)
One min./max. log -
One min./max./avg. log Min./max./avg. values recorded for 23 parameters
at regular intervals from 1 to 1440 minutes
One event log Time stamping to 1 ms, synchronisation 1 ms by GPS
Trend curves Four trend curves: 1 minute, 1 hour, 1 day and 1 month.
Min./max./avg. values recorded for eight parameters:
■ Every second for one minute for the 1-minute curve
■ Every minute for one hour for the 1-hour curve
■ Every hour for one day for the 1-day curve
■ Every day for one month for the 1-month curve
Forecasting Forecasting of the values for the eight parameters
for the next four hours and next four days
Waveform capture Standard: manual launch, 1 cycle, 128 samples, 63rd harmonic
Disturbance: manual launch or by alarm, 128 samples per cycle,
adjustable from 12 to 80 cycles, response time less than 0.5
cycle, number of cycles before alarm settable from 2 to 10
Alarms Adjustable pickup and dropout setpoints and time delays,
numerous activation levels possible for a given type of alarm.
Four priority levels, three response times: standard 1 second,
fast 100 ms, disturbance < 0.5 cycle (CM3350 only)
Boolean combination of four alarms is possible using the
operators NAND, OR, NOR and XOR Digital alarms, e.g. status
change of digital inputs
Memory 8 MB standard
Firmware update Update via the communication ports
Display characteristics
CMDLC (optional) Back-lit LCD
CMDVF (optional) Vacuum fluorescent display (VFD) with IR port
Languages French, English, Spanish
(1) Category II for distribution systems higher than 277/480 V.
(2) All the communication ports may be used simultaneously.