25
PM800 series with I/O module
Safety
Europe
U.S. and Canada
Communication
RS 485 port
Firmware characteristics
Data logs
Min./max.
One event log
Trend curves (PM850 only)
Forecasting (PM850 only)
Waveform capture
Alarms
Memory available for logging and
waveform capture
Firmware update
Display characteristics
73 x 69 mm
Languages
CE, as per IEC 61010
UL508
2- wire, up to 38400 bauds, Modbus
PM820 and PM850 (Optional in PM810)
1 Billing log
1 Customisable log
PM850 only
2 additional custom logs
Worst minimum and maximum with phase
indication for voltages, currents, voltage
unbalance, and THD.
Minimum and maximum values for power
factor (true and displacement), power
(P, Q, S) and frequency
Time stamping to 1 second
Four trend curves: 1 minute, 1 hour,
1 day and 1 month
every second for one minute for the
1-minute curve
every minute for one hour for the
1-hour curve
every hour for one day for the
1-day curve
every day for one month for the
1-month curve
Forecasting of the values for the trended
parameters for the next four hours and
next four days
Triggered manually or by alarm, 3-cycle,
128 samples/cycle on 6 user configurable
channels
adjustable pickup and dropout
setpoints and time delays, numerous
activation levels possible for a given
type of alarm
four priority levels
response time: 1 second
Boolean combination of four alarms is
possible using the operators NAND,
OR, NOR and XOR on PM850
Digital alarms, e.g. status change of
digital inputs
80 kbytes in PM820 and PM810MLOG
800 kbytes in PM850
Update via the communication ports
Back-lit white LCD
(6 lines total, 4 concurrent values)
English, French, Spanish