Specifications
PowerLogic:
Power meter series PM800
24
PM800 series back view
Electrical characteristics
Type of measurement
Measurement Current and voltage
accuracy Power
Frequency
Energy PM810
PM820 and
PM850
Data update rate
Input-voltage Measured voltage
characteristics
Metering over-range
Impedance
Frequency measurement range
Input-current CT ratings Primary
characteristics Secondary
Measurement input range
Permissible overload
Impedance
Load
Control Power AC
DC
Ride-through time
Input/outputs Pulse output
Status Input
Mechanical characteristics
Weight
IP degree of protection (IEC 60529)
Dimensions (mm)
Environmental conditions
Operating Meter
temperature Display
Storage Meter +
temperature Display
Humidity rating
Pollution degree
Metering category
Dielectric withstand
Electromagnetic compatibility
Electrostatic discharge
Immunity to radiated fields
Immunity to fast transients
Immunity to impulse waves
Conducted immunity
Immunity to magnetic fields
Immunity to voltage dips
Conducted and radiated emissions
Harmonics emissions
Flicker emissions
(1) 65 °C if control power is above 305 V AC
True rms up to the 63rd harmonic
On three-phase AC system (3PH, 3PH+N)
128 samples per cycle
±0.075% of reading + ±0.025% of full scale
±0.015% of reading + ±0.025% of full scale
±0.01 Hz from 45 to 67 Hz
±0.01 Hz from 350 to 450 Hz
IEC 61036 Class 1
IEC 60687 & ANSI C12.20 Class 0.5S
1s
0 to 600 V AC (direct L-L)
0 to 347 V AC (direct L-N)
0 to 3.2 MV AC (with external VT)
1.5 Un
2 MΩ L-L / 1 MΩ L-N
45 to 67 Hz and 350 to 450 Hz
Adjustable from 5A to 327 kA
1A or 5 A
0 to 10 A
15 A continuous
50 A for 10 seconds per hour
500 A for 1 second per hour
< 0.1 Ω
< 0.15 VA
100 to 415 ±10 % V AC, 11 VA
125 to 250 ±20 %V DC, 6 W
45 ms at 120 V AC
Static output (6 to 220 ±10% V AC or 3 to 250
±10 % V DC, 100 mA max. @ 25 °C)
1350 V rms isolation
1 digital input (24 to125 ±10 % V AC/DC),
5 mA max. burden
0.6 kg
IP52 front display, IP30 meter body
96x96x88 (meter with display)
96x96x70 (behind mounting surface)
-25 °C to +70 °C
(1)
-10 °C to +50 °C
-40 °C to +85 °C
5 to 95 % RH at 40 °C (non-condensing)
2
III, for distribution systems up to 347 V L-N /
600 V AC L-L
As per EN61010, UL508
Level III (IEC 61000-4-2)
Level III (IEC 61000-4-3)
Level III (IEC 61000-4-4)
Level III (IEC 61000-4-5)
Level III (IEC 61000-4-6)
Level III (IEC 61000-4-8)
Level III (IEC 61000-4-11)
CE industrial environment/FCC
part 15 class A
EN55011
IEC 61000-3-2
IEC 61000-3-3