Specifications
PowerLogic:
Power meter series PM700
17
PM700 series back view
Electrical characteristics
Type of measurement True rms up to the 15th harmonic
On three-phase AC system (3P 3P + N)
32 samples per cycle
Measurement Current and voltage 0.5 %
accuracy Power 1 %
Frequency ± 0.01 Hz from 45 to 65 Hz
Real Energy IEC 61036 Class 1
Reactive Energy IEC 61036 Class 2
Data update rate 1 s
Input-voltage Measured voltage 10 to 480 V AC (direct L-L)
characteristics 10 to 277 V AC (direct L-N)
0 to 3.2 MV AC (with external VT)
Metering over-range 1.2 Un
Impedance 2 MΩ (L-L) / 1 MΩ (L-N)
Frequency range 45 to 65 Hz
Input-current CT ratings Primary Adjustable from 5A to 65534 A
characteristics Secondary 5 A starting at 10 mA
Measurement input range 0 to 6 A
Permissible overload 15 A continuous
50 A for 10 seconds per hour
120 A for 1 second per hour
Impedance < 0.1 Ω
Load < 0.15 VA
Control Power AC 110 to 415 ±10 % V AC, 5 VA
DC 125 to 250 ±20 % V DC, 3 W
Ride-through time 100 ms at 120 V AC
Output Pulse output PM700P Static output (240 ±10 % V AC or 300 ±
10% V DC, 100 mA max. @ 25 °C, derate 0.56 mA
per °C above 25°C) 2.41 kV rms isolation
Mechanical characteristics
Weight 0.37 kg
IP degree of protection (IEC 60529) IP52 front display, IP30 meter body
Dimensions 96 x 96 x 88 mm (meter with display)
96 x 96 x 50 mm (behind mounting surface)
Environmental conditions
Operating Meter -0 °C to +60 °C
temperature Display -10 °C to +50 °C
Storage temp. Meter + display -40 °C to +85 °C
Humidity rating 5 to 95 % RH at 50 °C (non-condensing)
Pollution degree 2
Metering category III, for distribution systems up to 277 V L-N /
480 V AC L-L
Dielectric withstand As per EN61010, UL508
Electromagnetic compatibility
Electrostatic discharge Level III (IEC 61000-4-2)
Immunity to radiated fields Level III (IEC 61000-4-3)
Immunity to fast transients Level III (IEC 61000-4-4)
Immunity to impulse waves Level III (IEC 61000-4-5)
Conducted immunity Level III (IEC 61000-4-6)
Immunity to magnetic fields Level III (IEC 61000-4-8)
Immunity to voltage dips Level III (IEC 61000-4-11)
Conducted and radiated emissions CE commercial environment/FCC part 15 class B
EN55011
Harmonics emissions IEC 61000-3-2
Flicker emissions IEC 61000-3-3
Safety
Europe CE, as per IEC 61010-1
U.S. and Canada UL508
Communication
RS 485 port 2-wire, up to 19200 bauds, Modbus RTU
Firmware characteristics
Min./max. Worst min. and max. with phase indication for
voltages, currents, voltage unbalance, and THD. Min.
and max. values for power factor (True and
Displacement), power (P, Q, S) and frequency
Firmware update Update via the communication ports
Display characteristics
Dimensions 73 x 69mm Back-lit green LCD (6 lines total, 4 concurrent values)