Specifications
PowerLogic:
Branch power meter
13
Specifications
Operating temperature range 0 to 60
0
C (<95%RH non-condensing)
Storage temperature range -40
0
C to 70
0
C
Power source 240 VAC (+10V-10%) line to neutral 50Hz
Measured current inputs
Number of channels 24
Frequency 50Hz
Sample frequency 1280Hz
Update rate 1.2 sec
Accuracy +/- 1% of reading 2A to 32A
Network communications
Type Modbus RTU
Connection DIP switch selectable 2 wire or 4 wire
Address DIP switch selectable address 1 to 247
Baud rate DIP switch selectable 2400, 4800, 9600, 19200
Parity DIP switch selectable none, odd, even
Communication format 8 data bits, 1 start bit, 1 stop bit
Termination 9 pin sub D connector
TX+TX-shield TX+/RX+TX-/RX-
Defaults
Warning alarm register 60% of current setting (configurable)
Critical alarm register 30% of current setting (configurable)
Current settings 20A (configurable from 10 - 50A)
Dimensions (mm)
Circuit boards BPM
Strips 502 x 34 x 49
Mainboard 408 x 262 x 95
Sensor spacing 36 on centre
Hole opening 10