PowerLogic selection guide and technical overview
PowerLogic: Metering and monitoring for each level of your power system As a leading supplier of electrical distribution and power monitoring equipment Merlin Gerin has the portfolio of products required for each level on your electrical network. Comprehensive PowerLogic metering can provide real-time and event information to help mitigate and diagnose problems effectively and efficiently.
PowerLogic: Metering and monitoring devices Enterprise level Modbus Ethernet TCP/IP Critical circuits G G 33kV CM4000 M 33kV M 11kV 11kV M M Mains feeders M M 11kV M 11kV 11kV 415V 415V CM3000 Sepam 415V M M M Micrologic M Secondary feeders M M UPS PM800 M M M PM700 Distributed circuits M PM700 Key: G = Generator M = Meter M Branch power meter UPS = Uninterruptible Power Supply 3
PowerLogic: Metering and monitoring devices At Schneider Electric, we have the most complete and the most advanced line of power monitoring products for each level of your power system. Products like the award winning PowerLogic CM4000T circuit monitor and the unparalleled PowerLogic Power Server help keep you at the forefront of metering and monitoring technology.
PowerLogic: Network solutions Schneider Electric are at the forefront of the integration of web technologies into electrical distribution equipment through the deployment of Transparent ReadyTM. Transparent Ready utilises Ethernet TCP/IP to bring all the benefits of web based technology and open networking systems to the the PowerLogic system.
PowerLogic: Accessories to expand your system Extend the functionality of your PowerLogic system with input/output modules or our range of easy to add accessories including Ethernet connection cards, current and voltage modules and input/output extensions. Ethernet communication card The ECC is an optional ethernet communication card and can be installed in either the CM3000 or CM4000.
PowerLogic Metering device selection Selection of the correct devices for your PowerLogic system is essential to maximise the benefits available. The table on the following pages displays all the features available on PowerLogic metering devices. Further information can be found in the technical pages that follow.
PowerLogic: Metering device selection Power meters Branch PM700 power PM710 meter** Basic instrumentation Current, per phase Current, neutral Current, 3 phase average Current demand, max., per phase Current demand, max.
Power meters Branch power meter** PM700 PM710 Alarming Setpoint-driven alarms V,KW,KVA,I,PF,KVAR Boolean Digital inputs/outputs High speed (100ms) Disturbance (10msec) Transient (1microsec) Communications RS-485 RS-232 Onboard ethernet Infrared port ■ I/O KYZ/KY output Digital inputs/outputs, (maximum) Analogue inputs/outputs, (maximum) Time stamping accuracy PM710 PM700P Circuit monitors PM810 PM820 PM850 CM3250 CM3350 CM4000 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ CM4000T ■ ■ ■ ■
PowerLogic Multi-circuit metering The metering of multiple circuits is more and more common place in various applications, increased since the introduction of the building regulations part L2 as part of the climate change program introduced as UK legislation. The branch power meter provides a cost effective solution for single phase electrical load management making it ideally suited for applications where load capacity requirements are dynamic such as growing data centre and telecommunications industries.
PowerLogic: Branch power meter The branch current monitoring system provides a cost effective solution for electrical load management, making it ideally suited for applications where load capacity requirements are dynamic, such as power distribution units (PDU’s) for the data centre industry. The branch power meter reports the current level and power of each outgoing circuit from a panelboard or PDU providing preventative maintenance and consumption information on the users desktop PC.
PowerLogic: Branch power meter Specifications Operating temperature range Storage temperature range Power source 0 to 600C (<95%RH non-condensing) -400C to 700C 240 VAC (+10V-10%) line to neutral 50Hz Measured current inputs Number of channels Frequency Sample frequency Update rate Accuracy 24 50Hz 1280Hz 1.
PowerLogic: Branch power meter Branch power meter connection details ■ Monitor up to 24 circuits on 1 phase RS 485 Metering Input Control Power B A N Protection A N ■ Monitor up to 12 circuits on 2 phases RS 485 Metering Input Control Power B A N Protection A B N Branch power meter connection dimensions (mm) ■ Data acquisition board ■ Solid core CT strip 408 262 34 502 Overall height = 49 (DIN rail mounted) Overall height = 95 14
PowerLogic Power metering The PowerLogic range features an extensive range of panel mounting power meters offering a number of advantages over traditional analogue meters. All power meters within the PowerLogic range are cost effective, high performance metering devices that can operate as stand alone devices or as part of an overall PowerLogic system.
PowerLogic: Power meter series PM700 The PowerLogic power meter series 700 is an inexpensive and compact 96 x 96 mm unit that offers all the basic measurement capabilities required to monitor an electrical installation. With its large easy-to-read display, the meter can display all three phases and neutral at the same time. The anti-glare and scratch resistant display features an intuitive interface with self-guiding menus.
PowerLogic: Power meter series PM700 Electrical characteristics Type of measurement Measurement accuracy Data update rate Input-voltage characteristics PM700 series back view Input-current characteristics Control Power Output Current and voltage Power Frequency Real Energy Reactive Energy Measured voltage Metering over-range Impedance Frequency range CT ratings Primary Secondary Measurement input range Permissible overload Impedance Load AC DC Ride-through time Pulse output True rms up to the 15th
PowerLogic: Power meter series PM700 Selection guide General Use on LV and HV systems Current and voltage accuracy Energy and power accuracy PM700 PM710 PM700P ■ 0.5% 1.0% ■ 0.5% 1.0% ■ 0.5% 1.
PowerLogic: Power meter series PM700 4 wire connection with 3 CT’s and no VT PM700 3 wire connection with 2 CT’s and 2 VT’s PM700 19
PowerLogic: Power meter series PM700 Series PM700 dimensions Dimension in mm 20
PowerLogic: Power meter series PM700 Front panel mounting Dimension in mm 21
PowerLogic: Power meter series PM800 The PowerLogic PM800 series is a high performance power monitoring unit, providing all the measurement capabilities required to monitor an electrical installation in a single 96 x 96 mm unit. With its large, easy-to-read display, you can monitor all three phases and neutral at the same time. In addition, the anti-glare and scratch resistant display features an intuitive interface with self guiding menus.
PowerLogic: Power meter series PM800 2 1 3 Selection guide General Use on LV and HV systems Current and voltage accuracy Energy and power accuracy Number of samples per cycle Instantaneous rms values Current, voltage, frequency Active, reactive, apparent power Power factor Total and per phase Total and per phase Energy values Active, reactive, apparent energy Settable accumulation mode 4 Demand values Current 5 Active, reactive, apparent power 6 1 Control power supply connector 2 Voltage inputs
PowerLogic: Power meter series PM800 Electrical characteristics Type of measurement Measurement accuracy PM800 series back view Data update rate Input-voltage characteristics Input-current characteristics Control Power Input/outputs True rms up to the 63rd harmonic On three-phase AC system (3PH, 3PH+N) 128 samples per cycle Current and voltage ±0.075% of reading + ±0.025% of full scale Power ±0.015% of reading + ±0.025% of full scale Frequency ±0.01 Hz from 45 to 67 Hz ±0.
PowerLogic: Power meter series PM800 Safety Europe U.S. and Canada CE, as per IEC 61010 UL508 Communication RS 485 port 2- wire, up to 38400 bauds, Modbus Firmware characteristics Data logs PM800 series with I/O module Min./max.
PowerLogic: Power meter series PM800 Power meter PM800 Front panel mounting Clearances for multiple power meters Dimensions in mm 26
PowerLogic: Power meter series PM800 3 phase 4 wire direct voltage input connection 3 CT’s 3 phase 3 wire 2 CT’s 2 PT 27
PowerLogic: Current transformers Current transformers for use with PowerLogic range of Power Meters and circuit monitors. Technical data ■ Secondary current: 5A ■ Maximum voltage rating Ue: 720V ■ Frequency: 50 - 60Hz ■ Permanent permissible overload: 1.
PowerLogic: Current transformers Ordering details Ratio 40/5 50/5 75/5 100/5 125/5 150/5 200/5 250/5 300/5 400/5 500/5 600/5 800/5 1000/5 1250/5 1500/5 2000/5 2500/5 3000/5 4000/5 5000/5 6000/5 Cat no. standard 16501 16502 16503 16504 16505 16509 16506 16510 16526 16511 16518 16527 16512 16519 16528 16513 16520 16529 16514 16521 16523 16530 16515 16524 16531 16532 16533 Cat no.
PowerLogic: Current transformers Part numbers 16500 to 16506 and 16451 to 16456 44 Part numbers 16509 to 16515 and 16459 to 16465 Part numbers 16518 to 16521 and 16468 to 16471 77 40 56 30 42 30 46 65 21 84 107 33 88.5 22 10 27 111.5 42.
PowerLogic Circuit monitoring The PowerLogic range of circuit monitors offers multifunctional, digital instrumentation, data acquisition and control capable of replacing a variety of meters, relays, transducers and other components. The PowerLogic circuit monitor products install onto a three phase circuit like a conventional watt hour meter, but delivering far more information. The circuit monitors offer comprehensive metering with 0.04% typical accuracy on current and voltage.
PowerLogic: Circuit monitor series 3000 Circuit monitor CM3250 and CM3350 are high performance acquisition and control devices offering numerous measurement functions. They integrate easily in power monitoring and control systems due to their optional ethernet connections and embedded web server. Whether installed at the point of common coupling, at the head of a switchboard or on sensitive equipment feeders, circuit monitor units record the electrical parameters of the installation.
PowerLogic: Circuit monitor series 3000 CM3250 0.1 % 0.5 % 128 CM3350 0.1 % 0.5 % 128 ■ ■ ■ ■ ■ ■ ■ ■ Present and max. values Present and max.
PowerLogic: Circuit monitor series 3000 The CM3000 has two optional display units, an LCD display and a vacuum fluorescent display (VFD). They may be used for local circuit-monitor setup and operation. 1 Display screen 2 Infrared port (VFD display only) 3 Alarm LED 4 Arrow buttons 5 Menu button 6 Proximity sensor (VFD display only) 7 Enter button 8 Contrast button CMDLC display Back lit LCD display with four lines and 20 characters per line.
PowerLogic: Circuit monitor series 3000 Ethernet ECC21 communication card This optional card has two main functions: Ethernet ECC21 communication card ■ It provides the circuit monitor with a fast ethernet connection over a 10/100 Mbits/s copper link or a 100 Mbits/s Fibre optic link ■ It serves as an ethernet gateway for devices daisy chained to its RS485 Modbus port The card also includes a server for six HTML pages that may be consulted by a standard web browser.
PowerLogic: Circuit monitor series 3000 Electrical characteristics Type of measurement Measurement accuracy Current and voltage Power Frequency Energy Data update rate Input voltage characteristics Input current characteristics Supply Input/outputs Series 3000 + optional ECC21 or IOC44 36 Measured voltage Measurement range Impedance Frequency Measurement range CT ratings Measurement range Permissible overload Impedance Load AC DC Ride through time Pulse output IOC44 card (optional) True rms up to
PowerLogic: Circuit monitor series 3000 Mechanical characteristics Weight IP degree of protection (IEC 60529) Dimensions (mm) 1.
PowerLogic: Circuit monitor series 3000 Ethernet ECC21 card with HTML server (optional) (2) Copper ethernet link 10/100 BaseTX, RJ45 connector, 100-metre link Fibre-optic ethernet link 100 Base FX, LC duplex connector, 1300 nm, FO multimode with gradient index 62.
PowerLogic: Circuit monitor series 3000 3 wire connection with 2 CT’s and no VT 4 wire connection with 4 CT’s and 3 VT’s Ethernet ECC21 communication card IOC44 input/output card 39
PowerLogic: Circuit monitor series 3000 CM3000 Mounting on symmetrical rail Dimensions in mm 40
PowerLogic: Circuit monitor series 3000 CMDLC/CMDVF Mounting on a back plate Dimensions in mm 41
PowerLogic: Circuit monitor series 4000 The CM4000 and CM4000T are high performance, digital instrumentation, data acquisition and control devices offering numerous measurement functions and easy integration due to their ethernet connections and embedded web server. They are designed for applications where power quality and availability are critical factors. They are generally used at the service entrance and for sensitive equipment mains.
PowerLogic: Circuit monitor series 4000 Selection guide General Use on LV and HV systems Current and voltage accuracy Energy and power accuracy Nbr of samples/cycle or sample frequency Instantaneous rms values Current, voltage, frequency Active, reactive, apparent power Power factor Total and per phase Total and per phase Energy values Active, reactive, apparent energy Settable accumulation mode 1 Current/voltage module 2 Control power-supply connector 3 Maintenance LED indicator 4 Power LED indica
PowerLogic: Circuit monitor series 4000 The CM4000 has two optional display units, an LCD display and a vacuum fluorescent display (VFD). They may be used for local circuit monitor setup and operation. 1 Display screen 2 Infrared port (VFD display only) 3 Alarm LED 4 Arrow buttons 5 Menu button 6 Proximity sensor (VFD display only) 7 Enter button 8 Contrast button CMDLC display Back lit LCD display with four lines and 20 characters per line.
PowerLogic: Circuit monitor series 4000 Ethernet ECC21 communication card The ECC21 is an optional ethernet communication card. It may be installed in one of the two slots in the circuit monitor intended for optional cards. It has two main functions: ■ Equip the circuit monitor with a fast ethernet connection over a 10/100 Mbits/s copper link or a 100 Mbits/s Fibre optic link ■ Serve as an ethernet gateway for devices daisy chained to its RS485 Modbus port.
PowerLogic: Circuit monitor series 4000 Input/output blocks may be added to the circuit monitor to: ■ Monitor the electrical installation, notably the status of the circuit breakers, and check discrimination between protection devices ■ Measure the consumption of other commodities by counting the pulses sent by water or gas meters ■ Measure the temperature of the transformers ■ Transmit parameters over analogue channels to other systems The circuit monitor may be equipped with a total of 25 optional
PowerLogic: Circuit monitor series 4000 IOX input/output extender The IOX input/output extender may be equipped with up to eight plug-in input or output modules. The entire unit connects to the side of the circuit monitor. The input/output modules may be digital or analogue. Three pre-equipped versions may be ordered directly, the IOX08, IOX0404 and IOX2411. Other versions may be user prepared by ordering an empty IOX extender and separate I/O modules (see the section on I/O Modules for selection).
PowerLogic: Circuit monitor series 4000 Electrical characteristics Type of measurement Measurement accuracy Current and voltage Power Frequency Power factor Energy Data update rate Input-voltage characteristics Input-current characteristics Power supply Input/outputs Measured voltage Measurement range Impedance Frequency measurement range CT ratings Measurement range Permissible overload Impedance Load AC DC Ride through time Pulse output IOC44 card (optional) IOX extender (optional) IOX08 (optiona
PowerLogic: Circuit monitor series 4000 Mechanical characteristics Weight IP degree of protection (IEC 60529) Dimensions (mm) Without accessories CM4000 With accessories Dimensions Without accessories CM4000T With accessories 1.9 kg IP52 231.4 x 231.4 x 231.4 x 231.4 x 152.2 202.9 165.6 216.3 x x x x 133.1 133.1 133.1 133.
PowerLogic: Circuit monitor series 4000 Safety Europe USA and Canada Communication RS485 port (1) RS232 port (1) a PC or modem Infrared port (optional) (1) CE, as per IEC 61010 UL508 and CSA C22.
PowerLogic: Circuit monitor series 4000 3 wire connection with 2 CT’s and no VT 4 wire connection with 4 CT’s and 3 VT’s 51
PowerLogic: Circuit monitor series 4000 Ethernet ECC21 communication card IOC44 input/output card 52 IOX input/output extender
PowerLogic: Circuit monitor series 4000 CM4000 CM4000T Dimensions in mm 53
PowerLogic: Circuit monitor series 4000 Mounting on a back plate series 4000 Mounting possibilities Vertical mounting Horizontal mounting CMDLC/CMDVF Mounting on a back plate Dimensions in mm 54
PowerLogic Network solutions Transparent ReadyTM from Schneider Electric is an open network framework based upon internet technologies to provide seamless communications between operational plant and business systems. The network solution from PowerLogic provides an essential building block to Transparent Ready along with Programmable Logic Controllers (PLC’s), Human Machine Interfaces (HMI’s) and motor controllers, including Variable Speed Drives (VSD’s).
PowerLogic: EGX Ethernet gateways The EGX 200 and EGX 400 make ethernet communications available to the devices in the PowerLogic system. The EGX 400 gateway also includes HTML pages that may be accessed via a standard internet browser. These HTML pages may be used to display information transmitted by the devices connected to the gateway. The internet browser may also be used to set the EGX gateway communication links and to update the imbedded software.
PowerLogic: EGX Ethernet gateways Characteristics Control power input specifications Operating input range Burden, maximum Isolation 24Vdc (±10%) 8 watts 1.
PowerLogic: EGX Ethernet gateways Communications overview PowerLogic system manager software Standard web browser Ethernet TCP/IP EGX RS 485 daisy chain connected to the EGX RS 485 port CM4000 PM700 PM800 Sepam Altivar 38/58 variable speed drive Micrologic Connection details Communications wiring (4 wire) with Belden 8723 cable COM 1 (RS 485) 10 9 Rx- 8 Rx+ Shield Black COM 2 (RS 485) 7 Tx- 6 5 3 2 RS 485 1 TX TX RX RX Tx+ Red 4 Rx- White Green Rx+ Shield Black Tx- Tx+
PowerLogic: EGX Ethernet gateways Wiring details stems PowerLogic sy COM 1 (RS 485) 100 Base FX 10-100 Base T COM 2 (RS 485) LK TX RX 24V - 8W 24V dc control power connector Common +24V dc 24V dc switching power supply (included with EGX) To ground earth Dimensions (mm) 45 123 37 201 11 221 Top view 201 28 15 End view 45 78 11 28 50 201 15 Side view 59
PowerLogic: Power Server Designed for unattended operations in industrial or large commercial buildings. The power server from PowerLogic is a self contained information server that can be a stand alone system providing local monitoring or part of a corporate enterprise. In either capacity, the power server functions as a power monitoring web server, data concentrator and a communications gateway connecting and displaying information for up to 64 monitoring devices in the PowerLogic system.
PowerLogic: Power Server Specifications Control power input specification Operating input range Burden, maximum Environment Ambient operating temperature Ambient storage temperature Sealing Altitude (maximum) Physical specifications Housing dimensions (mm) Weight Isolation Regulatory/standards compliance EMC 24V DC (± 10%) (sourced by Class 2 rated supply) 28W 0 to 500C (<95% relative humidity, non-condensing) -200C to 700C IP30: sealed against particles >2.5mm 4.
PowerLogic: Power Server Specifications Part number Power Server data can be sent to a web system server to enable total energy consumption analysis per site as well as company wide peak contributions for all locations.
PowerLogic: Power Server Communications overview The Power Server used as a stand alone system monitoring device Web browser Initial set up via net meeting Device set up for the PowerLogic system Ethernet Optical touch screen EGX Mixed mode daisy chain Power Server used as a component of the PowerLogic system The Power Server used as a gateway device with SMS and a web server View reports via web browser Internet PowerLogic enterprise system Internet PC with system manager software (SMS) Web
PowerLogic: Power Server Connection details 1 2 3 5 1 COM 1 - RS 232 serial port set up connection 2 COM 2 - RS 232 touchscreen serial connection 3 UTP port 4 VGA output to touchscreen monitor 5 COM 3 - RS 485 port 6 COM 4 - RS 485 port 7 Control power Typical 4 wire connection (IN+) 64 RX+ (IN-) RX- (OUT+) TX+ (OUT-) TX- (Shld) Shield 6 7 Typical 2 wire connection DB9F2TB to Power Server 4 wire typical standard PowerLogic Slave device 4 DB9F2TB to Power Server 2 wire typ
PowerLogic: Power Server Dimensions (mm) 3 14 228 92 65
PowerLogic Glossary of terms
PowerLogic: Glossary of terms Accumulated energy Energy can accumulate in either signed or unsigned (absolute) mode. In signed mode, the direction of power flow is considered and the accumulated energy magnitude may increase and decrease. In absolute mode, energy accumulates as a positive regardless of the power flow direction. Ethernet address A unique number that identifies the device in the Ethernet network and is always written as a combination of eleven or twelve numbers such as 199.186.195.23.
PowerLogic: Glossary of terms Partial interval demand Calculation of energy thus far in a present interval. Equal to energy accumulated this far in the interval divided by the length of the complete interval. Peak demand current Highest demand current measured in amperes since the last reset of demand. See also peak value. Peak demand real power Highest demand real power measured since the last rest of demand. Peak demand voltage Highest demand voltage measured since the last reset of demand voltage.
Nationwide support on one number call the Customer Information Centre on 0870 608 8 608 Fax 0870 608 8 606 Schneider Electric’s local support Schneider Electric is committed to supporting its customers at every stage of a project. Our 180 sales engineers, the largest dedicated sales force in the UK electrical industry, operate from 4 customer support centres.