User guide
PowerLogic™ PM5300 series user guide  Chapter 7—Alarms
© 2014 Schneider Electric All Rights Reserved70
Setting Up Digital Alarms
To set up digital alarms:
1. Press Dig. The digital alarm 
Select screen appears.
2. Press ▼ and ▲ to scroll 
through the list of digital 
alarms.
3. Press Edit to select an alarm to 
be configured.
4. Press Edit to select Pickup 
Setpoint, then press Edit.
5. Press + and - to scroll between 
On and Off.
6. Press OK to enter the pickup 
setpoint.
7. Press ▼ to select Pickup Time 
Delay, then press Edit.
NOTE: If the selected status 
input mode is Demand Sync or 
Input Metering, a confirmation 
screen appears warning that if 
an alarm is enabled for this 
status input, the existing 
association will be broken.
8. Press + to increment the active 
digit through the numerals 0-9.
NOTE: Units for time delays 
are set in seconds.
9. Press  to enter the selected 
value for the active digit and 
move to the next digit to the 
left.
10. Continue until all values are 
selected, then press OK to 
enter the pickup time delay.
11. Press 
▼ to select Dropout 
Time Delay, then press Edit.
12. Follow Steps 8 to 11 for the 
dropout time delay.