User guide
PowerLogic™ PM5300 series user guide  Chapter 5—Viewing Meter Data
© 2014 Schneider Electric All Rights Reserved 47
Related topics
• See “Power quality” on page 89.
Related topics
• See “Alarms” on page 63.
Related topics
• See “Input / Output” on page 49.
PF
True Per phase and total true power factor values and sign.
Disp Per phase and total displacement power factor values and sign.
Hz [F]
Frequency (Freq), average voltage and current (Vavg, Iavg) and power factor (PF) values.
THD
THD
THD (ratio of harmonic content to the fundamental) for current, 
line-to-line voltage, and line-to-neutral voltage.
Amps [I], V L-L [U], V L-N [V]
thd thd (ratio of harmonic content to the rms value of total harmonic 
content) for current, line-to-line voltage, and line-to-neutral 
voltage.
Amps [I], V L-L [U], V L-N [V]
Unbal
Percent unbalance readings for line-to-line voltage (V L-L [U]), line-to-neutral voltage (V L-N [V]) and current 
(Amps [I]).
MnMx
MnMx
Summary of maximum values for line-to-line voltage, line-to-
neutral voltage, phase current and total power.
Amps [I] Minimum and maximum values for phase current.
Volts
Minimum and maximum values for line-to-line voltage and line-
to-neutral voltage.
VL-L, VL-N
Power
Minimum and maximum values for active, reactive, and apparent 
power.
Active, Reac, Apr
PF
Minimum and maximum values for true and displacement PF and 
PF sign.
True, Disp
Hz Minimum and maximum values for frequency.
THD
Minimum and maximum values for total harmonic distortion (THD 
or thd).
THD, thd
Amps, VL-L, VL-N
THD or thd minimum and maximum values for phase or neutral 
current, line-to-line voltage and line-to-neutral voltage.
Unbal
Minimum and maximum values for current unbalance, line-to-line 
voltage unbalance and line-to-neutral voltage unbalance..
Amps, VL-L, VL-N
Alarm
Active, Hist, Count, Unack
Lists all active alarms, past alarms (Hist), the total number each 
standard alarm has been tripped (Count), and all 
unacknowledged alarms.
I/O
D Out Current status (on or off) of the selected digital output, status 
input or relay. Counter shows the total number of times an off-to-
on change of state is detected. Timer shows the total time (in 
seconds) that a digital output, status input or relay is in the on 
state.
S In
Relay