Specifications
Power Meter 750  63230-507-201A1
Section 6—Alarms 03/2007
© 2007 Schneider Electric All Rights Reserved28
ALARM SETUP  When making alarm setup changes using the display, evaluation of all 
alarms is temporarily suspended while alarm setup screens are displayed. 
Evaluation resumes immediately upon exit from the alarm setup screens.
Setting Up Alarms  The following sequence may be used to set up an alarm:
Setting Up Magnitudes and Delays  After changing an alarm’s status, a screen for changing the pickup and 
dropout magnitudes and delay values is displayed.
Digital 
14 Digital Input OFF/ON DIGITAL INPUT S1 4115
15 Digital Input OFF/ON DIGITAL INPUT S2 4116
Table 6– 1: List of Default Alarms by Alarm Number (continued) 
Alarm 
Number
Alarm 
Description
Abbreviated
Display Name
Test 
Register
1. In SETUP mode, press ###: until ALARM 
is visible.
2. Press ALARM.
3. Using the 
<-- and --> buttons, scroll 
through the alarms until you reach the 
alarm(s) you want to set.
4. Press EDIT to change the ENABL value. 
The value will start to blink.
5. Press 
+ to toggle the On/Off setting. 
Press OK to select. To set up magnitude 
and delay values, see below.
6. Press
1; return to the SETUP MODE 
screen. 
/6%2#522%.4
 /+
$)!'
%.!",
!,
1. Enter the PU MAG value (pickup 
magnitude). Press OK.
2. Enter the PU DELAY value (pickup delay 
in seconds). Press OK.
3. Enter the DO MAG value (dropout 
magnitude). Press OK.
4. Enter the DO DELAY value (dropout 
delay in seconds). Press OK.
5. Press
1; return to the SETUP MODE 
screen
. 