Set Up Demand Current and Power 
Set Up the Passwords
1. In SETUP mode, press ###: until DMD 
(demand) is visible.
2. Press DMD (demand setup).
3. Enter the MIN (demand interval in 
minutes) for I (current): 1 to 60.
4. Press OK. 
5. Enter the MIN (demand interval in 
minutes) for P (power): 1 to 60.
6. Press OK. 
7. Enter the SUB-I (number of sub-
intervals) for P: 1 to 60.
8. Press OK
 to return to the SETUP 
MODE screen.
NOTE: The calculation method used for 
current is Thermal.
NOTE: The calculation method used for 
power is based on SUB-I as follows:
• 0 = sliding block
• 1= block
• >1 = rolling block (The SUB-I value must 
divide evenly into the MIN value. For 
example, if MIN is 15, SUB-I can be 3, 
5, or 15. If you selected 3, you would 
have 3 sub-intervals at 5 minutes each.