User`s guide

MBX Driver Help
Cyberlogic Technologies Inc. - 70 -
Setting Words Per Node To Read
Select an
MB+ Node
intended to receive global data. Click the
Edit
button or right-click
and select
Edit
from the menu. Select the number of words of global data to read from
the list and press
Enter
.
Specific Outputs Configuration
Note
Peer Cop communications can send up to 32 words of specific output data to each
node on a Modbus Plus network. The total amount of specific output data sent from all
applications through a single host interface adapter must not exceed 500 words.
For every specific output word configured, you can specify the default data that the
driver will use before an application overwrites it. By default, all specific output data
words are filled with 0.
You can also configure what action the driver should take when a user application exits,
either normally or abnormally. The specific outputs controlled by this application are
either left in their last state or restored to a pre-configured default state by the driver.
Setting Words Per Node To Write
Select an
MB+ Node
intended to receive specific output data. Click the
Edit Words
button or right-click in the
Words Per Node
column and select
Edit
from the context
menu. Finally select the number of words to write from the list and press
Enter
.