User`s guide

MBX Driver Help
Cyberlogic Technologies Inc. - 106 -
devices in the system.
Invalid configuration parameter. One of the requested system resources (such as the
memory address or interrupt IRQ), has already been allocated to a different device.
Mapping selected interrupt into system interrupt vector for <device name>
failed. Check device configuration and restart the driver.
Unreported interrupt already used by another device driver.
Mapping selected physical memory address to logical address space for
<device name> failed. Check device configuration and restart the driver.
Unreported memory range already used by another device driver.
Not enough memory in <paged/nonpaged> pool was available to allocate
internal storage needed for <Device Name>. Close some applications. Add
more memory to your system.
Memory allocation from the specified memory pool failed. This is a fatal error. The driver
will not load.
Parameter <parameter name> for device <device name> has invalid value
(<value>). Check device configuration and restart the driver.
Invalid configuration parameter. This is a fatal error.
Parameter <parameter name> for device <device name> has invalid value
(End of dump data has parameter value). Check device configuration and
restart the driver.
Invalid configuration parameter. This is a fatal error.
The bus number selected for device <device name> is not supported by this
computer system.
Invalid configuration parameter.
The <device name> failed to communicate to the adapter card. Check the
selected memory range for the card and make sure that the card is plugged in.
Also, check Resources under Windows NT Diagnostics for possible conflicts
with other devices in the system.
The device driver is unable to communicate to the selected adapter card.