User`s guide
MBX Driver Help
Cyberlogic Technologies Inc. - 102 -
MBX Driver Messages
The USB adapter for <Device Name> failed the dual-port memory diagnostics.
Try another adapter card.
This indicates a hardware failure.
The USB adapter for <Device Name> failed interface diagnostics. Try another
adapter card.
This indicates a hardware failure.
The USB adapter for <Device Name> failed peer cop initialization. Check peer
cop configuration and restart the driver. Try another adapter card.
This indicates a hardware failure.
The USB adapter for <Device Name> failed to power up. Check device
configuration and restart the driver. Try another adapter card.
This indicates a hardware failure.
The USB adapter for device <Device Name> has reported corrupted firmware.
To correct this, reload the module's firmware from the Device Manager, then
disconnect and reconnect the USB adapter.
The firmware for the TSXCUSBMBP is corrupted. To reload the firmware, open the device
in Windows Device Manager and go to the Firmware tab.
Device <Device Name> has entered the USB Loader mode. The normal
operation of this device has been disabled. To resume normal operation,
disconnect and reconnect the USB adapter. If the problem persists, reload the
module's firmware from the Device Manager.
In Loader mode, the TSXCUSBMBP cannot perform its normal operations. Disconnect it
to restore it to normal mode.
Parameter <Parameter Name> for device <Device Name> has invalid size
(End of dump data has size value). Check device configuration and restart the
driver.
This indicates an error in the configuration of the specified MBX device. Correct the
configuration and restart the driver.