Specifications

Bulletin No. VVDED397044US R12/00 Section 1—Installation & Configuration
December 2000 Interface Specifications
© 1998–2000 Schneider Electric All Rights Reserved
7
SECTION 1—INSTALLATION & CONFIGURATION
RECEIVING, PRELIMINARY INSPECTION, AND STORAGE
After receiving the VW3A58302U communication option card:
Ensure that the catalog number printed on the box label is the same
as that on the packing slip and corresponding purchase order. Contact
your local Square D representative if there are any errors.
Observe the following precautions for handling static sensitive
components as the card is removed from its packaging for inspection.
Keep static producing material (plastic, upholstery, carpeting, etc.)
out of the immediate work area.
Avoid touching exposed conductors and component leads with
skin or clothing.
If any damage is found, notify the carrier and your local Square D
representative.
To store the option card, replace it in its original package (including the
anti-static bag) and store it at -40 to 185 °F (-40 to 85 °C).
COMMUNICATION INTERFACE SPECIFICATIONS
Table 4: MODBUS PLUS Option Card Specifications
Isolation (network to drive controller) Galvanically isolated for 30 V RMS, 50 V peak
Isolation (cable jacket to ground) 150 V RMS
Connector 9-pin, female D-shell
Electrical interface RS-485
Storage temperature -40 to 185 °F (-40 to +85 °C)
Operating temperature
Same as drive controller. See
VVDED397048US.
Humidity
< 95% relative humidity at +140 °F (+60 °C),
non-condensing
Altitude Up to 15,000 ft (4,500 m)
Shock (non-operating) 30 g for 11 ms (three shocks/axis)
Shock (operating)
Same as drive controller. See
VVDED397048US.