SECTION 1—INSTALLATION & CONFIGURATION
RECEIVING, PRELIMINARY INSPECTION, AND STORAGE
After receiving the VW3A58302U communication option card:
• Ensure that the catalog number printed on the box label is the same
as that on the packing slip and corresponding purchase order. Contact
your local Square D representative if there are any errors.
• Observe the following precautions for handling static sensitive
components as the card is removed from its packaging for inspection.
— Keep static producing material (plastic, upholstery, carpeting, etc.)
out of the immediate work area.
— Avoid touching exposed conductors and component leads with
skin or clothing.
• If any damage is found, notify the carrier and your local Square D
representative.
• To store the option card, replace it in its original package (including the
anti-static bag) and store it at -40 to 185 °F (-40 to 85 °C).
COMMUNICATION INTERFACE SPECIFICATIONS
Table 4: MODBUS PLUS Option Card Specifications
Isolation (network to drive controller) Galvanically isolated for 30 V RMS, 50 V peak
Isolation (cable jacket to ground) 150 V RMS
Connector 9-pin, female D-shell
Electrical interface RS-485
Storage temperature -40 to 185 °F (-40 to +85 °C)
Operating temperature
Same as drive controller. See
VVDED397048US.
Humidity
< 95% relative humidity at +140 °F (+60 °C),
non-condensing
Altitude Up to 15,000 ft (4,500 m)
Shock (non-operating) 30 g for 11 ms (three shocks/axis)
Shock (operating)
Same as drive controller. See
VVDED397048US.