Specifications

Section 2—Modbus Plus Overview Bulletin No. VVDED397044US R12/00
Forced Local December 2000
54
© 1998–2000 Schneider Electric All Rights Reserved
When the logic input is not active (low), all control of the drive is
transferred to the network if wired as shown in Figures 28 or 29. The only
local (hand) controls that are still monitored by the drive controller include
the logic input assigned to Forced Local and any input assigned to a drive
stop function. Examples include:
the stop button on the keypad display
logic input one (LI1) which is assigned to the function STOP if the
ATV58 drive controller is configured for 3-wire control
any logic input assigned to the functions freewheel stop, DC injection
braking, and fast stop.
See the keypad display manual VVDED397047US (latest revision) for
more details.
Communication Fault Monitoring
Word 402, bit 14 of command register CMI is used to inhibit
communication fault responses. If bit 14 = 1, the drive controller ignores
communication errors from the serial link. This function is intended for
use during troubleshooting and start-up. Do not use this function
during normal network operation.
UNINTENDED EQUIPMENT ACTION
When in forced local mode, all commands from the communication
ports are ignored.
Failure to consider the implications of unanticipated operation
can result in death, serious injury, or equipment damage.
WARNING
UNINTENDED EQUIPMENT ACTION
Loss of communication will not cause the drive controller to fault.
Failure to consider implications of unanticipated operations can
result in death, serious injury, or equipment damage.
WARNING