Local and Remote
The ATV58 drive controller can be commanded in local and remote
control modes.
Local Control
In local (hand) control, the drive controller is controlled by either:
Operators such as push buttons, switches, and a speed potentiometer
that are wired to the drive controller terminal block
The keypad display buttons
See the latest revision of the keypad display manual VVDED397047US
for more details on how to select between the two modes of local control.
Remote Control
In remote (auto) control:
The drive controller is controlled by the serial communication network.
The speed reference and the start/stop control cannot come from
separate sources.
Forced Local
Switching between local and remote control is achieved by a switch wired
to a logic input on the controller terminal block as illustrated in Figure 28
on page 52 and Figure 29 above. The logic input must be assigned to the
function, forced local.
When the logic input assigned to forced local is active (high), all control
of the drive controller is assigned to the selected local (hand) control
mode. In this case, command requests by the network are refused.
Command parameters can be monitored. All other parameters can be
read/write accessed.