Specifications
Section 2—Modbus Plus Overview Bulletin No. VVDED397044US R12/00
Hand/Off/Auto (HOA) December 2000
52
© 1998–2000 Schneider Electric All Rights Reserved
before the MODBUS PLUS communication board has initialized and
assumed control.
This can result in unintended equipment operation.
When the control switch is in the hand or off position,
the drive controller
must be placed into the forced local mode .
While it is possible to stop
the drive controller in the remote mode by activating one of the local stop
commands (such as the keypad display stop button), commands sent
over the network can restart the drive controller if it is not in forced local
mode. See “Forced Local” on page 53.
Refer to Figures 28 and 29 for assistance in designing Hand/Off/Auto
control. For the run reverse and forced local functions, select any unused
logic inputs on the main control board. Assign a logic input to the run
reverse function only if appropriate for the application.
Figure 28: Example 2-Wire Control
NOTE: When the HOA switch is in the auto position, removing the local
run forward or run reverse commands does not stop the drive controller.
Figure 29: Example 3-Wire Control
Hand Off Auto
LI1 Run Forward
+24
LIx Run Reverse
LIy Forced Local
User
Control
Scheme
Hand Off Auto
+24
Stop
Fwd Rev
LI1 Stop
LI2 Run Forward
LIx Run Reverse
LIy Forced Local