Specifications
Bulletin No. VVDED397044US R12/00 Section 2—Modbus Plus Overview
December 2000 Hand/Off/Auto (HOA)
© 1998–2000 Schneider Electric All Rights Reserved
51
• through a PLC or other controller connected to the fast serial link via a
communication card
NOTE: The operator keypad takes priority over the terminals.
When the communication network has control of the drive, the setpoints
and commands are controlled via the network and cannot be modified by
the terminals, the keypad, or any device connected to the RS-485
MODBUS serial port. To command the drive controller by the terminals,
the keypad, or any device connected to the RS-485 MODBUS serial port,
forced local must be enabled.
Hand/Off/Auto (HOA)
When the control switch is in the auto position,
all local run and start
commands to the drive controller must be removed.
During power-up,
the ATV58 drive controller defaults to local control. (See “Local and
Remote” on page 53.) After the drive controller recovers from a power up
sequence (including such unplanned events as an AC line power
disturbance), it immediately responds to any local controls that are active
UNINTENDED EQUIPMENT ACTION
When in serial link/line mode, all terminal inputs are ignored except
digital inputs configured as stop functions.
Failure to consider the implications of unanticipated operations
can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
The user must provide a Hand/Off/Auto switch with the following
functionality:
• In the Hand position, forced local mode must be enabled.
• In the Off position, all run terminal inputs must be disabled via
open circuit, and forced local mode must be enabled.
• In the Auto position, the run terminal inputs must be disabled via
open circuit, and forced local mode must be disabled.
Failure to follow these instructions can result in death or serious
injury.
WARNING