Specifications
Bulletin No. VVDED397044US R12/00 Section 2—Modbus Plus Overview
December 2000 Command Semaphore
© 1998–2000 Schneider Electric All Rights Reserved
49
— Change TLP using the operator keypad or the PC software.
— Perform steps 6 and 7 to set the motor to RUN FORWARD.
12. The other nodes on the network can read all of the drive controller
registers via message handling. They cannot write to the registers
used in peer cop (in this example, they are the five registers CMD,
LFR, CMI, HSP, LSP). However, they can write to other adjustment
registers (ACC, DEC, etc.).
COMMAND SEMAPHORE
The command semaphore is a means of identifying which device the
drive controller receives its commands from. The drive controller can be
controlled locally by the logic on the terminal strip, the keypad, by the
MODBUS port the keypad plugs into, or through a fast serial link (PLC for
example). There is no configurable semaphore between the terminal
strip, the keypad, the MODBUS port, or a fast serial link.
An implicit command semaphore exists between the network nodes. If
peer cop data is enabled, none of the stations connected to the network
can write to control words. It is possible to take the command semaphore
only when peer cop data is disabled, or the drive controller is in CNF fault
mode without having lost the token. When peer cop data is disabled, the
first node to write via message handling to control words 400, 401, and
402 automatically takes the command semaphore. The drive controller
responds to this write operation by implicitly taking the command
semaphore. Only the node reserving the semaphore in this way can write
to control words. The semaphore remains reserved as long as the node
writes or reads at least once during the time-out period specified in the
8—Communication menu.
The command semaphore is released by writing bit 8 of word 400 to a
value of 1 within the specified time. Otherwise, the semaphore is freed if
no write/read operation takes place and the drive controller switches to
CNF fault mode.
NOTE: If peer cop data is again received from the network, the node
which has implicitly taken the command semaphore automatically loses
it and all requests to write to the control words via message handling are
refused by the drive controller.
The MODBUS PLUS port takes priority over the MODBUS port; if the
MODBUS PLUS port is active the drive controller’s control words cannot
be written through the MODBUS port. However, other devices can still
write to configuration words and read display words through the
MODBUS port. The MODBUS PLUS control device can release control