Specifications
Section 2—Modbus Plus Overview Bulletin No. VVDED397044US R12/00
Global Data Transmission December 2000
48
© 1998–2000 Schneider Electric All Rights Reserved
3. Power up the drive controller.
4. Adjust the five MODBUS PLUS parameters using the operator
keypad or the PC software (part number VW3A8104).
— TLP: Peer cop time-out. Factory setting 1 s. Change the setting if
necessary. Disconnecting the PLC or the drive controller for this
duration will stop the motor and the drive controller will switch to
CNF fault mode.
— CDN: Control node. Factory setting is 0. Set this parameter to 3 to
correspond to the address of the PLC which is to control the drive
controller via peer cop.
— REG: Number of peer cop registers received from the PLC.
Factory setting is 0. Set this parameter to 5 (five registers received
from the PLC). Note that other stations can no longer write to
these five peer cop registers via message handling.
1st peer cop register = CMD control word (Run, Stop, Reset, etc.)
2nd peer cop register= LFR speed reference word
3rd peer cop register = CMI integral control word
4th peer cop register = HSP high speed limit
5th peer cop register = LSP low speed limit
— GLB: Number of global data registers sent on the network. Factory
setting is 0. Set this parameter to 14 (14 registers sent to the
network and read by the PLC).
— PRC: Factory setting is No. Set this parameter to Yes to use peer
cop.
5. To fix the speed reference at 25 Hz, set LFR to 250 (second peer cop
register sent by the PLC).
6. Bring the drive controller from “ATV58 On and Locked” to “Standby
Status” by setting CMD to 6 and waiting until the ETA (word 458) is
equal to 21.
7. Next set the drive controller to “Ready” state. Set CMD to 7 and wait
until the 9th global data register ETA is XX23h.
8. Bring the drive controller to “Running” state by setting CMD to 0F for
forward or 80F for reverse and wait until the ETA (word 458) is equal
to 27h.
9. To set the drive controller to STOP, set CMD = 100 Fh.
10. If the drive controller is in CNF fault mode (register ETA = XXX8h), to
reset it via the network set CMD to 80h. Then perform steps 6 and 7
to rotate the motor.
11. To change the Time-Out parameter TLP:
— Stop the motor by setting CMD to 100 Fh.