DIAGNOSTICS
The MODBUS PLUS option card has one LED that indicates the status
of the communication link.
Figure 26: LED Location
Table 9: LED States
State of LED Meaning
Off
Card Disabled: Switch 7 is in ON state
ILF Fault: A communication problem exitst between the
communication option card and the drive controller.
1 flash per second
Monitor Link: On powering up or after exit from “4 flashes
per second” mode, the card monitors the network and
constructs a table of nodes which are active and hold a
token. At the end of 5 seconds, the card attempts to switch
to normal operating status (indicated by 6 flashes per
second).
6 flashes per second
Token OK: The token is circulating normally and the card
is receiving it once per rotation.
2 flashes per second followed
by a pause of 2 seconds
Never Getting Token: The token is passing via other
nodes, but the card never receives it.
3 flashes per second followed
by a pause of 1.7 seconds
Sole Station: The network only contains one node or the
link has been lost.
4 flashes per second followed
by a pause of 1.4 seconds
Duplicate Station: Another node is using the card address.
The card is waiting for reconfiguration or for the other node
to be disconnected from the network.