Specifications
Section 1—Installation & Configuration Bulletin No. VVDED397044US R12/00
Hardware Setup December 2000
12
© 1998–2000 Schneider Electric All Rights Reserved
Figure 3: Card Layout
HARDWARE SETUP
Setting the Drive Controller Address
An ALTIVAR 58 drive controller is identified on the MODBUS PLUS
network by its unique address, which can range from 1 to 64.Select the
address by setting DIP switches on the option card. Refer to Figure 4 on
page 13 for details and examples.
Switches 1–6 collectively make up a binary number, and the address is
determined by adding 1 to that binary number. In other words, each
switch corresponds to a value as shown in Figure 4. The address is
determined by adding the values corresponding to each switch set to 1
(on) and then adding 1.
NOTE: The drive controller updates an address from the switch setting on
power-up.
2
1
1
0
1
8
LED
Address Switches
Connector