Specifications

Section 1—Installation & Configuration Bulletin No. VVDED397044US R12/00
Bus Voltage Measurement Procedure December 2000
8
© 1998–2000 Schneider Electric All Rights Reserved
BEFORE INSTALLING THE OPTION CARD
Before installing, removing, or replacing the MODBUS PLUS option card,
remove all power from the drive controller, including external control
power that may be present on the option module, and perform the “Bus
Voltage Measurement Procedure” on page 8.
BUS VOLTAGE MEASUREMENT PROCEDURE
Before installing the VW3A58302U communication card, measure the
bus voltage as described in this section.
The DC bus voltage level is determined by monitoring the (+) and (–)
measurement points. Their location varies by drive controller model
number as listed in Table 5 on page 9. The drive controller model number
is listed on the nameplate.
UNINTENDED EQUIPMENT ACTION
Read and understand documents VVDED397048US and
VVDED397047US before operating the drive controller.
Failure to follow this instruction can result in death, serious
injury, or equipment damage.
WARNING
DANGER
HAZARDOUS VOLTAGE
Read and understand the bus voltage measurement procedure
before performing the procedure. Measurement of bus capacitor
voltage must be performed by qualified personnel.
DO NOT short across capacitors or touch unshielded
components or terminal strip screw connections with voltage
present.
Many parts in this drive controller, including printed wiring boards,
operate at line voltage. DO NOT TOUCH. Use only electrically
insulated tools.
Electrical shock will result in death or serious injury.