Estimating Network Performance
890 USE 100 00
87
3. Calculate the global data acquisition time
Each unit’s time to receive data from another unit’s Global Data Write
would be:
Average time 1/2 token rotation time 10.59 ms
1/2 scan time of the receiving unit 10 ms
Total 20.59 ms
Worst case time 1 token rotation time 21.18 ms
1 scan time of the receiving unit 20 ms
Total 41.18 ms