User manual

Magelis B - 33
4. Application pages
B
The PLC dialog table contains the "Page to be processed" word (1). The
display unit reads the dialog table in the PLC (2) and displays the desired
page (3).
Once the command has been processed, the display unit writes the
value "H’FFFF’" in the "Page to be processed" word (4), which tells the
PLC program that the display request has been acknowledged.
From system pages
System pages are used to display application pages.
For more information about access to system pages, see section "6.
System pages", Page 39.
Scrolling within a page
Scrolling is necessary to view the whole of a page, which contains more
lines than the screen is capable of displaying. On display, the first n (n
being the number of lines on the display unit) lines on the page are
displayed. For example, four lines for the XBT N400 display unit.
XBT ref. Note
N200 No scrolling
N400/N401/N410
NU400
For display units in “input” mode only
LIST OF PAGES
LIST OF ALARMS